Objects and Properties
7.3.3. OnOff_command (Binary Output Object Type)
It turns the indoor unit on or off.
Property Identifier
Object_Identifier
Object_Name
Object_Type
Present_Value
Description
Device_Type
Status_Flags
Event_State
Reliability
Out_Of_Service
Polarity
Inactive_Text
Active_Text
Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
Minimum_Off_Time
Minimum_On_Time
Priority_Array
Relinquish_Default
Time Delay
Notification_Class
Feedback_Value
Event_Enable
Acked_Transitions
Notify_Type
Event_Time_Stamps
Profile_Name
USER MANUAL Version 1.2.6
Property Datatype
BACnetObjectIdentifier
CharacterString
BACnetObjectType
BACnetBinaryPV
CharacterString
CharacterString
BACnetStatusFlags
BACnetEventState
BACnetReliability
BOOLEAN
BACnetPolarity
CharacterString
CharacterString
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned
BACnetDatetime
Unsigned32
Unsigned32
BACnetPriorityArray
BACnetBinaryPV
Unsigned
Unsigned
BACnetBinaryPV
BACnetEventTransitionBits
BACnetEventTransitionBits
BACnetNotifyType
BACnetArray[N] of BACnetTimeStamp
CharacterString
IN485MIT001I000 Gateway
Value
(Binary Output, 0)
OnOff_command
BINARY_OUTPUT (4)
INACTIVE (0) / ACTIVE (1)
-
-
{FALSE, FALSE, FALSE, FALSE}
STATE_NORMAL (0)
NO_FAULT_DETECTED (0)
FALSE
NORMAL (0)
Off
On
-
-
-
-
-
-
-
BACnetPriorityArray
INACTIVE (0)
-
-
-
-
-
-
-
-
ASHRAE
Gateway
R
R
R
R
R
R
R
W
O
-
O
-
R
R
R
R
O
R
R
R
R
R
O
R
O
R
O
-
O
-
O
-
O
-
O
-
O
-
O
-
R
R
R
R
O
-
O
-
O
-
O
-
O
-
O
-
O
-
O
-
Page 19 of 55