61000-4-5
61000-4-6
61000-4-8
61000-4-11
61000-4-12
61000-4-16
61000-4-17
61000-4-29
RUGGEDCOM RS900
Equipment Manual, 11/2023, C79000-G8976-1024-16
Test
IEC
Surge
IEC
Induced (Conducted) RFI
IEC
Magnetic Field
IEC
Voltage Dips and Interrupts
IEC
Damped Oscillatory
IEC
Mains Frequency Voltage
IEC
Ripple on DC Power Supply
IEC
Voltage Dips and Interrupts
6.2 EMC and Environmental Type Tests
Description
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Earth
Ground Ports
Enclosure
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
AC Power
Ports
Signal Ports
DC Power
Ports
DC Power
Ports
DC Power
Ports
Certification
Test Levels
± 4 kV
± 4 kV
± 4 kV
± 4 kV Line-to-Ground
± 2 kV
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m Continuous
1000 A/m for 1 s
100% for 5 Periods
100% for 50 Periods
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
2.5 kV Common
Mode @ 1 MHz
1 kV Differential
Mode @ 1 MHz
30 V Continuous
300 V for 1 s
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Severity
Levels
4
4
4
4
3
4
3
3
3
3
 
 
3
3
3
4
4
3
 
35