4-2 Function Mode
User Parameter Automatic Setting Function
•When user parameter automatic setting function b039 is set to "01" (enabled), the parameters
subjected to a data change are automatically stored in sequence (from U001 to U012). This data
can be used as changed data.
•The screen information is stored when the Enter key is pressed. The monitor screens (d***) are
also stored in the same manner.
•U001 is the most recent parameter, and U012 is the oldest.
•The same parameter cannot be stored. If the number of parameters stored exceeds 12, the oldest
data (U012) is erased.
Parameter No.
4
b039
Related functions
Torque Limit Function
•This function limits motor output torque when "03" (sensorless vector control), "04" (0-Hz
sensorless vector control), or "05" (sensor vector control) is selected in control method A044/A244.
Parameter No.
A044/A244
b040
b041
b042
b043
b044
C001 to C008
C021 to C025
Related functions
4-57
Function name
User parameter automatic
setting function selection
Function name
03: Sensorless vector
V/f characteristics
04: 0-Hz sensorless vector
selection
05: Sensor vector (A244 is blank.)
00: Four-quadrant separate setting
01: Terminal switch
Torque limit selection
02: Analog input
03: Option 1
04: Option 2
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
Torque limit 1
Forward power running
under four-quadrant separate setting
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
Torque limit 2
Reverse regeneration
under four-quadrant separate setting
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
Torque limit 3
Reverse power running
under four-quadrant separate setting
0. to 200. (0.4 to 55 kW)
0. to 180. (75 to 132 kW)
Torque limit 4
Forward regeneration
under four-quadrant separate setting
40: Torque limit enabled
Multi-function inputs
41: Torque limit switching 1
1 to 8 selection
42: Torque limit switching 2
Multi-function output
10: During torque limit
terminal selection
Data
00: Disabled
01: Enabled
U001 to U012
Data
A044, A244, C001 to C008
Default setting
Unit
00
Default setting
Unit
00
00
150.
%
150.
%
150.
%
150.
%