2-3-3 Temperature controller communications settings
This summarizes temperature controller communications settings.
For more details on settings and operation procedure of setting specifications, refer to the
relevant temperature controller manual.
■ E5ZN
Setup Switch on E5ZN panel
Unit number
Baud rate
Communications setting level
Data bits
Stop bits
Parity
Response
Waiting time
■ E5GN/E5AN/E5EN/E5CN/E5ER/E5AR
Adjustment level L.Adj
Communications
writing
Communications setting level L.S
Baud rate
Data bits
Stop bits
Parity
Response
Waiting time
Communications
Unit No.
Protocol select
6
When using multiple E5ZN units, be
0 to 15
careful not the use the same number
twice.
0
1
2
CH
C3 0013 or
C3 0113
C3 0014 or
C3 0114
C3 0015 or
C3 0115
C3 0016 or
0 to 270FH
C3 0116
CoWt
on
OFF
bPS
2.4
4.8
9.6
19.2
38.4
LEn
7
Sbit
2
Prty
EvEn
SdWt
0 to 270FH
( 0 to
9999 )
U-no
0 to 31
PSEL
CyF
4800
Bps
9600
Bps
19200
Bps
Value
7
7 bits
2
2 bits
2
Even (EvEn)
In ms
( 0 t o
9999)
enable
disable
In kbps
Set all communicating temperature
controllers to match parameters of NS
E5ER/AR: choose between
9.6/19.2/38.4
E5□N: 38.4 cannot be selected.
7 bits
2 bits
Even
In ms
E5AR/ER range: 0 to 63H(0 to 99)
E5AR/ER only
Compoway/F (E5AR/ER only)