Receiver Troubleshooting; Receiver Error Codes - Omron MS4800E - MANUAL 2 Operation Manual

Safety light curtain type 4
Hide thumbs Also See for MS4800E - MANUAL 2:
Table of Contents

Advertisement

Receiver Troubleshooting

17-4 Receiver Troubleshooting

17-5 Receiver Error Codes

Code Group
Error Code
Configuration
21
Switch Faults
22
23
24
26
Safety Output
31
(OSSD) Faults
32
33
34
35
EDM Faults
41
42
43
44
Controller Fault
50
Setup Error
60
Muting Faults
70
71
74
72
If the yellow INTERLOCK LED is blinking:
1. Check the configuration for External Device Monitoring. If EDM is inactive
(via receiver dip switch), the input (pink wire) must be connected to system
ground. If EDM is active, the input must be connected to the normally
closed contacts of the control relays of the guarded machine or the monitor
terminal of the safety relay unit. Please refer to SECTION 11 Connection
to the Machine Control Circuit for an example.
2. Make sure both selector switches in the receiver endcap have been set
properly and identically. Please refer to chapter 7-2 Operating mode selec-
tion for further information.
3. Verify the power supply is within the specified limits (+24V ±20%).
4. Verify the light curtain is properly connected to the control relays of the
guarded machine. If the light curtain is not intended to be connected to
control relays, see SECTION 12 Muting for further information.
5. Verify the control relays are within operating limits of the safety outputs.
6. Verify the cable lengths from the light curtain to the control relays are within
specified limits.
7. If this does not solve the problem, please contact your local Omron distrib-
utor or the European Repair Center.
Description of Error Code
Invalid mode selection setting
Configuration switch settings changed dur-
ing operation
Configuration switch settings do not match
Corrupted EEPROM configuration
Invalid scan code setting
Safety outputs 1&2 are shorted together
Safety output 1 is shorted to power
Safety output 2 is shorted to power
Safety output 1 is shorted to ground
Safety output 2 is shorted to ground
EDM circuit did not open before transition to
MACHINE RUN state
EDM circuit did not open after transition to
MACHINE RUN state
EDM circuit was in wrong state during
power-up
EDM fault at power-up
Control logic fault
Possible crosstalk
General muting fault
Mute module enable and configuration
required:
Mute lamp burned out or not connected
Corrective Action Needed
Verify switch setting, see user manual
Verify switch setting, see user manual
Verify switch setting, see user manual
Reset the system configuration to factory
defaults
Verify switch setting, see user manual
Check and correct wiring of safety outputs 1
and 2
Check and correct wiring of safety outputs 1
Check and correct wiring of safety outputs 2
Check and correct wiring of safety outputs 1
Check and correct wiring of safety outputs 2
Check and correct EDM wiring
Check and correct EDM wiring
Check and correct EDM wiring
Check start input wire or EDM function
selection
Please contact your local Omron distributor
or the European Repair Center
Check and correct scan code setting
Check wiring of unused mute sensors
Check mounting of mute sensors for correct
sequence
Check status of mute lamp
Section 17-4