Calibration Flowchart
(K3HB-S)
User calibration is performed according to the following flowchart.
User calibration is performed for input A if "A" is included in the
calculation and input B if "B" is included in the calculation. Calibration
is performed on both inputs A and B if both "A" and "B" are included in
the calculation.
Input A included
in calculation.
Connect the calibrator and input A and turn ON the power supply.
Temporary registration of upper calibration limit for input A.
Temporary registration of lower calibration limit for input A.
Registration of temporarily registered input A calibration value.
Input B included
in calculation.
Connect the calibrator and input B.
Temporary registration of upper calibration limit for input B.
Temporary registration of lower calibration limit for input B.
Registration of temporarily registered input B calibration value.
Recalibrate.
Turn ON the power supply again
and check operation in RUN level.
The input type that can be calibrated according to this flowchart is the
type selected under "input type A" or "input type B." To calibrate other
input types, switch the setting for "input type A" or "input type B" in the
initial setting level to the desired input type and then perform
calibration according to the flowchart outlined above.
6.1 About User Calibration
Input A not included in calculation.
Move to the calibration level.
Aging
Input B not included in calculation.
Calibration finished.