Omron K3HB-H User Manual page 120

Digital indicators
Hide thumbs Also See for K3HB-H:
Table of Contents

Advertisement

Hysteresis is set using the following parameter.
f
hys
L
(HYS)
* The decimal point depends on the "decimal point position" setting.
Parameter Setting Procedure
Parameter
Hysteresis
hys
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
0" is displayed on the level/bank
• "
L
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to "amov."
• This parameter is not displayed for the
initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-102) for information on removing
setting level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
D Use the U [UP] and S [SHIFT] Keys
to set the password "-0169." Press the
M [MODE] Key to move to the
advanced function setting level.
f" is displayed on the level/bank
• "
L
display to indicate the advanced
function setting level.
E Press the M [MODE] Key several times
to change the PV display to "hys."
F Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
G Use the U [UP] and S [SHIFT] Keys
to change the set value.
5.16 Preventing Output Chattering
Set value
Meaning of set value
0 to 9999
0 to 9,999 *
L
3 s min.
M
S
U
S
M
M
S
U
S
0
L
0."
Displays "
L
amov
0
L
0
amov
0
L
00000
init
f
L
off
f."
Displays "
L
hys
f
L
1
hys
f
L
0001
hys
f
L
0050
5-47