Specifications - Omron H5F Datasheet

Digital daily time switch
Hide thumbs Also See for H5F:
Table of Contents

Advertisement

Specifications

Ratings
Rated supply voltage
Operating voltage range
Power consumption
Control outputs
External connections
Terminal screw tightening torque
Characteristics
Accuracy of operating time
Setting error
Influence of voltage
Influence of temperature
Cyclic error
Memory protection
Insulation resistance
Dielectric strength
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Life expectancy
Approved safety standards
EMC
Case color
Weight
Note: 1. The total error including the repeat accuracy, setting error, variation due to voltage change, and variation due to temperature change is
± 0.01% ± 0.05 s max. ± 0.01% also indicates an error in the time interval of a set time.
2. The total time when power is not being supplied.
2
Digital Daily Time Switch
100 to 240 VAC (50/60 Hz)
85% to 110% of rated supply voltage
Approx. 2.4 VA at 264 VAC
Contact output: SPST-NO, 15 A at 250 VAC, resistive load, 10 A at 24 VDC, resistive load
Minimum applied load: 100 mA at 5 VDC (failure level: P, reference value)
NEMA A300 Pilot Duty, 1/3 HP at 120 VAC
Screw terminals (M3.5 screw)
0.98 to 1.17 N · m
± 0.01% ± 0.05 s max. (see note 1)
Monthly difference ± 15 s (at 25 ° C)
Continuous use: 5 years min. (at 25 ° C); Power-interruption rate of 50%: 10 years min. (at 25 ° C) (see note 2)
(lithium battery)
100 M W min. (between current-carrying terminals and exposed non-current-carrying metal parts, between operating
power supply circuit and control output circuit and between non-continuous contacts)
2,000 VAC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal parts and
between operating power supply circuit and control output circuit)
1,000 VAC, 50/60 Hz for 1 min (between non-continuous contacts)
1.5 kV (between power terminals)
Square-wave noise by noise simulator (pulse width: 100 ns/1 m s, 1-ns rise)
Destruction:10 to 55 Hz with 0.375-mm single amplitude, four cycles each in three directions (8 minutes per cycle)
Malfunction:10 to 55 Hz with 0.25-mm single amplitude for 10 minutes each in three directions
2
Destruction:300 m/s
3 times each in 6 directions
2
Malfunction:100 m/s
3 times each in 6 directions
Operating:–10 ° C to 55 ° C (with no icing)
Storage: –25 ° C to 65 ° C (with no icing)
Operating: 35% to 85%
Mechanical (at 20 ° C):
100,000 operations min.
Electrical (at 20 ° C):
50,000 operations min. (15 A, 250 VAC, resistive load)
50,000 operations min. (1 HP, 250 VAC, motor load)
50,000 operations min. (10 A, 250 VAC, inductive load (cos f = 0.7))
50,000 operations min. (100 W, 100 VAC, lamp load)
10,000 operations min. (300 W, 100 VAC, lamp load)
UL508/Listing, CSA C22.2 No. 14, conforms to EN61010-1 (Pollution degree 2/overvoltage category II)
Conforms to VDE0106/P100 (finger protection).
Conforms to Electrical Appliance and Material Safety Law (for Japan)
(EMI)
Emission Enclosure:
Emission AC mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Conducted
Disturbance:
Immunity Burst:
Immunity Surge:
Immunity Voltage Dip/Interruption:
Immunity Magnetic Power Field:
Light gray (Munsell 5Y7/1)
H5F-B: approx. 115 g; H5F-KB: approx. 160 g; H5F-FB: approx. 130 g
H5F
EN61326
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61326
EN61000-4-2:
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
EN61000-4-3:
10 V/m (Amplitude-modulated, 80 MHz to 1 GHz,
1.4 to 2 GHz) (level 3)
EN61000-4-6:
10 V (0.15 to 80 MHz) (according to EN61000-6-2)
EN61000-4-4:
2 kV power-line (level 3)
1 kV I/O signal-line (level 4)
EN61000-4-5:
1 kV line to lines (power and output lines) (level 2);
2 kV line to ground (power and output lines) (level 3)
EN61000-4-11: 0.5 cycle, 100% (rated voltage)
EN61000-4-8:
30 A/m