Characteristics
Item
Contact resistance (See note 2.)
Operating time (See note 3.)
Release time (See note 3.)
Maximum operating
Mechanical
frequency
Rated load
Insulation resistance (See note 4.)
Dielectric strength
Between coil and contacts
Between contacts of different polarity
Between contacts of the same polarity
Impulse withstand
Between coil and contacts
voltage
Between contacts of different polarity
Between contacts of the same polarity
Vibration resistance
Destruction
Malfunction
Shock resistance
Destruction
Malfunction
Endurance
Mechanical
Electrical (See note 5.)
Failure rate P value (reference value)
Ambient operating temperature
Ambient operating humidity
Weight
Note: 1. The above values are initial values.
2. The contact resistance for the Relay (G7Z) was measured with 1 A at 5 VDC using the voltage drop method.
The contact resistance for the auxiliary contact block (G73Z) was measured with 0.1 A at 5 VDC using the voltage drop method.
3. The operate time was measured with the rated voltage imposed with any contact bounce ignored at the ambient temperature of 23 C.
4. The insulation resistance was measured with a 1,000-VDC megohmmeter applied to the same places as those used for checking the dielectric strength.
5. The electrical endurance was measured at an ambient temperature of 23 C.
6. The specifications for the auxiliary contact block mounted on the G7Z are the same as those for the G73Z auxiliary contact block.
Approved Standards
UL Standard: UL508, UL840 (File No.
E41643)
Model
Coil
ratings
G7Z
12, 24 VDC NO
40 A, 480 VAC, 60 Hz
contact
(Resistive)
5 A, 120 VDC (Resistive)
22 A, 480 VAC, 60 Hz
(General Use)
D300* (1-A current applied) ---
NC
25 A, 480 VAC, 60 Hz
contact
(Resistive)
5 A, 120 VDC (Resistive)
10 A, 480 VAC, 60 Hz
(General Use)
D300* (1-A current applied) ---
Note: Auxiliary contact ratings
Model
G73Z
NO contact
NC contact
CSA Standard: CSA Certification by
: CSA C22.2 No. 14
6
Power Relays
Classification
Model
100 m
50 ms max.
50 ms max.
1,800 operations/h
1,200 operations/h
1,000 M min.
4,000 VAC, 50/60 Hz for 1 min
4,000 VAC, 50/60 Hz for 1 min
2,000 VAC, 50/60 Hz for 1 min
10 kV, 1.2
10 kV, 1.2
4.5 kV, 1.2
10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
NO: 10 to 55 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
NC: 10 to 32 to 10 Hz, 0.5-mm single amplitude (1.0-mm double amplitude)
Screw mounting: 800 m/s
NO: 100 m/s
NO: 25 m/s
1,000,000 operations min. (at 1,800 operations/h, contact no load)
AC resistive load: 80,000 operations
AC inductive load: 80,000 operations
DC resistive load: 100,000 operations
(at 1,200 operations/h, rated load)
2 A at 24 VDC
5% to 85%
Approx. 330 g
Contact ratings
Number of
test
operations
80,000
100,000
100,000
100,000
Contact ratings
D300 (1-A current applied)
G7Z
Relay (See note 6.)
G7Z-4A-@Z, G7Z-3A1B-@Z, G7Z-2A2B-@Z
max.
50 µs
50 µs
50 µs
2
, DIN Track mounting: 500 m/s
2
2
25 to 60 C (with no icing or condensation)
EN Standard/TÜV Certification: EN
60947-4-1 (Certification No. R50079155)
Model
Coil ratings
G7Z
12, 24 VDC
G73Z
---
Note: Auxiliary contact ratings
Reference Information
UL 508:
UL 840:
CSA C22.2 No. 14:
EN 60947-4-1:
Auxiliary contact block
G73Z-20Z, G73Z-11Z, G73Z-02Z
---
---
2
1 mA at 5 VDC
Contact ratings
NO contact AC-1: 40 A, 440 V, 50/60 Hz
AC-3: 16 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC15: 0.5 A, 440 V, 50/60 Hz
*DC13: 0.5 A, 110 V
NC contact AC-1: 25 A, 440 V, 50/60 Hz
DC-1: 5 A, 110 V
*AC15: 0.5 A, 440 V, 50/60 Hz
*DC13: 0.5 A, 110 V
NO contact AC15: 0.5 A, 440 V , 50/60 Hz
DC13: 0.5 A, 110 V
NC contact
Industrial control devices
Insulation coordination including clearance
and creepage distance for electrical devices
Industrial control devices
Contactors

Advertisement