Operation - Omron E5AK Datasheet

Digital controller
Hide thumbs Also See for E5AK:
Table of Contents

Advertisement

Operation

■ After Turning ON Power
Determine the I/O specifications of the Digital Controller in setup
mode.
Power ON
Process value
Temperature input
C/ F
selection
From next page
To next page
20
Digital Controller
1 s min.
1 s min.
Input type
Current/Voltage input
Scaling
upper limit
Scaling
lower limit
Decimal point
Parameter initialize
E5AK/E5EK
■ Input Type
Set the code according to the following table. Default is "2: K1 ther-
mocouple."
Platinum Resistance Thermometer
Set
value
0
JPt100
199.9 to 650.0 ( C)
/ 199.9 to 999.9 ( F)
1
Pt100
199.9 to 650.0 ( C)
/ 199.9 to 999.9 ( F)
2
K1
200 to 1,300 ( C)
/ 300 to 2,300 ( F)
3
K2
0.0 to 500.0 ( C)
/0.0 to 900.0 ( F)
4
J1
100 to 850 ( C)
/ 100 to 1,500 ( F)
5
J2
0.0 to 400.0 ( C)
/0.0 to 750.0 ( F)
6
T
199.9 to 400.0 ( C)
/ 199.9 to 700.0 ( F)
7
E
0 to 600 ( C)
/0 to 1,100 ( F)
8
L1
100 to 850 ( C)
/ 100 to 1,500 ( F)
9
L2
0.0 to 400.0 ( C)
/0.0 to 750.0 ( F)
10
U
199.9 to 400.0 ( C)
/ 199.9 to 700.0 ( F)
11
N
200 to 1,300 ( C)
/ 300 to 2,300 ( F)
12
R
0 to 1,700 ( C)
/0 to 3,000 ( F)
13
S
0 to 1,700 ( C)
/0 to 3,000 ( F)
14
B
100 to 1,800 ( C)
/300 to 3,200 ( F)
15
W
0 to 2,300 ( C)
/0 to 4,100 ( F)
16
PLII
0 to 1,300 ( C)
/0 to 2,300 ( F)
17
4 to 20 mA
18
0 to 20 mA
19
1 to 5 V
20
0 to 5 V
21
0 to 10 V
Input type
Platinum resistance ther-
mometer
Thermocouple
Current input
Voltage input

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5ek

Table of Contents