Changing The Cpm2A's Mode With The Mode Switch - Omron CPM2A - 11-2005 Manual

Programmable controllers
Table of Contents

Advertisement

Compatible Programming Consoles

4-1-1 Changing the CPM2A's Mode with the Mode Switch

MONITOR
RUN
PROGRAM
Mode display
Operation
Operating Modes
Caution
!
!
Caution
92
Once the Programming Console has been connected, its mode switch can be
used to change the CPM2A's operating mode. The mode display (<PRO-
GRAM>, <MONITOR>, or <RUN>) will appear on the Programming Console
screen.
• No key operations can be performed while the mode display is displayed on
the Programming Console screen. Press CLR to clear the display so that key
operations can be performed.
• If the SHIFT Key is pressed while the mode switch is turned, the original dis-
play will remain on the Programming Console's screen and the mode display
won't appear.
• The CPM2A will enter RUN mode automatically if a Programming Console
isn't connected when the CPM2A is turned on.
RUN
CLR
Initial display
PROGRAM Mode
The CPM2A program isn't executed in PROGRAM mode. Use PROGRAM
mode to create and edit the program, clear memory, or check the program for
errors.
MONITOR Mode
The CPM2A program is executed in MONITOR mode and I/O is processed just
as it is in RUN mode. Use MONITOR mode to test system operations, such as
monitoring CPM2A operating status, force-setting and resetting I/O bits, chang-
ing the SV/PV of timers and counters, changing word data, and online editing.
RUN Mode
This is the CPM2A's normal operating mode. The CPM2A's operating status can
be monitored from a Programming Device, but bits can't be force-set/force-reset
and the SV/PV of timers and counters can't be changed.
Check the system thoroughly before changing the operating mode of the PC to
prevent any accidents that might occur when the program is first started.
Never change the mode while pressing any of the keys.
MONITOR
PROGRAM
Operation
Section
MONITOR
RUN
PROGRAM
SHIFT
CLR
4-1