Omron CP1H CPU Operation Manual page 83

Cp1h cpu unit
Hide thumbs Also See for CP1H CPU:
Table of Contents

Advertisement

Specifications
Power supply
classification
Model numbers
• XA CPU Units
CP1H-XA40DR-A
• X CPU Units
CP1H-X40DR-A
Insulation resistance 20 MΩ min. (at 500 VDC) between the external
AC terminals and GR terminals
Dielectric strength
2,300 VAC 50/60 Hz for 1 min between the
external AC and GR terminals, leakage current:
5 mA max.
Noise resistance
Conforms to IEC 61000-4-4 2 kV (power supply line)
Vibration resistance
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
80 minutes each (time coefficient of 8 minutes × coefficient factor of 10 = total time of 80 minutes)
Shock resistance
147 m/s
Ambient operating
0 to 55°C
temperature
Ambient humidity
10% to 90% (with no condensation)
Atmosphere
No corrosive gas.
−20 to 75°C (excluding battery)
Ambient storage
temperature
Terminal screw size
M3
Power interrupt time
10 ms min.
Weight
740 g max.
Note
Characteristics
Type
Model
Program capacity
Control method
I/O control method
Program language
AC power supply
2
three times each in X, Y, and Z directions
The above values are for a cold start at room temperature for an AC power
supply, and for a cold start for a DC power supply.
• A thermistor (with low-temperature current suppression characteristics) is
used in the inrush current control circuitry for the AC power supply. The
thermistor will not be sufficiently cooled if the ambient temperature is high
or if a hot start is performed when the power supply has been OFF for
only a short time, so in those cases the inrush current values may be
higher (as much as two times higher) than those shown above.
• A capacitor delay circuit is used in the inrush current control circuitry for
the DC power supply. The capacitor will not be charged if a hot start is
performed when the power supply has been OFF for only a short time, so
in those cases the inrush current values may be higher (as much as two
times higher) than those shown above.
• Always allow for this when selecting fuses and breakers for external cir-
cuits.
X CPU Units
CP1H-X40DR-A
CP1H-X40DT-D
CP1H-X40DT1-D
20 Ksteps
Stored program method
Cyclic scan with immediate refreshing
Ladder diagram
• XA CPU Units
CP1H-XA40DT-D
CP1H-XA40DT1-D
• X CPU Units
CP1H-X40DT-D
CP1H-X40DT1-D
No insulation between primary and secondary
DC power supplies.
No insulation between primary and secondary
DC power supplies.
2 ms min.
590 g max.
XA CPU Units
CP1H-XA40DR-A
CP1H-XA40DT-D
CP1H-XA40DT1-D
Section 2-2
DC power supply
• Y CPU Units
CP1H-Y20DT-D
2
in X, Y, and Z directions for
560 g max.
Y CPU Units
CP1H-Y20DT-D
49