Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60 Core module version 55.04 - Build 05.21 | Touch control version 60.01 Build 01.39 Translation of original German version of service handbook for technicians. Read and follow all instructions and safety instructions.
4.3.1 Solar - Status ..........................46 4.3.2 Solar - Temperatures ......................... 48 4.3.3 Solar - Times..........................48 4.3.4 Solar - Service ........................... 49 4.3.5 Solar - Heat meter........................50 4.4 Buffer tank............................. 51 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 4
5.8.1 Carrying out a software update on the boiler controller ............. 107 5.8.2 Carrying out a software update on the touch control ..............109 5.8.3 Finishing a software update ....................... 110 5.9 USB data recording..........................111 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Insulate the flue gas pipes and do not touch them during operation The information on safety, standards and guidelines in the assembly and operating instructions for the boiler should also be observed! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Null modem cable 9-pin SUB-D; Connection is used e.g. as MODBUS interface KM-05 COM 1 Null modem cable 9-pin SUB-D; Service interface for software updates and connection to visualisation software B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 7
, max. 2A or burner relay KM-35 Operating signal Connection cable 2 x 0.75 mm Ü "Operating signal" [} 15] 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
In the delivered state, the outside temperature sensor is read in by the core module ("KM-19 / outside temperature sensor" connection). Alternatively, the outside temperature sensor can be connected to an additional heating circuit module. Ü "Heating circuit module" [} 16] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Allows you to adjust the temperature by +/- 3°C IMPORTANT! Refer to the supplied assembly instructions for more detailed explanations on connecting and operating the FRA room temperature sensor. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
The speed of HCP 0 is not controlled. (Observe the pump dimensions!) r Setting the “Continuous load” mode The higher level control system should ensure a minimum activation time of 15 minutes for the pellet boiler. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r Set control of the pump in the relevant menu to “Field pump / PWM” or “Field pump / 0-10V” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 12
30%). FRKEM29 AO-P1 r Connect pump to output “Pump 1” of the core module r In the relevant menu, set the pump control to “Pump without control signal” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r In the relevant menu, set the activation of the pump to “Field pump PDM + valve” or to “Field pump 0-10V + valve” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 14
Connect the phase (L) for switching over the valves together with the phase (L) for the pump to the switched output of the relay r In the relevant menu, set the pump control to “HE pump without control signal” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
4 x 0.75 mm , max. 0.15A / 230V HE-12 Mixing valve 2 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 Fuses 6.3 AT HE-09, HE-10, HE-11, HE-12 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Depending on the type of pump, the phase (L) is either connected to the relay output or triac output. Connecting a circulating pump to the hydraulic module 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 18
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r Set control of the pump in the relevant menu to “Field pump / PWM” or “Field pump / 0-10V” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 19
Connect the power supply for the pump to output “Pump 1” or “Pump 2” and use the triac output for phase r In the relevant menu, set the pump to “Pump without control signal” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 20
) from NOC on the relay to the pump using terminal “S/S” as the release contact r Connect power supply at pump connector r In relevant menu, set pump to “Field pump PDM + valve” or “Field pump 0-10V + valve” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 21
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r In the relevant menu, set the activation of the pump to “Field pump PDM + valve” or to “Field pump 0-10V + valve” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 22
(L) r Connect the phase (L) for continuous supply (switches the valve back to the initial position) to the power supply at terminal “L” B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
RL-05 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 Fuses 6.3 AT RL-01 Connection example Balancing valve Firewood-/ Return mixing valve Dual fuel boiler (Return mixer module) B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 26
Connect L and N of the power supply line for the pellet mole to the "COM" terminals of the relay switch contacts and wire from the "NO" terminals to the pellet mole B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 27
NOTICE! The return signal of the room air flap at input “Digi IN” must have a floating design. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
NOTICE! The inputs and output are pre-configured, so it is essential the following addressing is complied with. Standard configuration – Analogue module with address 0 Input Designation External power specification (0-10V) B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 29
(“Boiler release input available” parameter = YES). Necessary parameters for setting the power demand can be found in the “Boiler – General settings” menu. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
For the bus connections between the individual modules, cable type LIYCY paired 2x2x0.5 should be used. The connection to the 5-pin plugs should be carried out according to the following diagram: Braided shield Braided shield white white green green yellow yellow brown brown B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If the contacts at the base of the end jumper are not bridged (image left), it is referred to as “not set". In this case there is no bus termination. If the contacts are closed (image right), the end jumper is set and the bus connection is terminated. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Connect the control cable to the PDM output on the board, making sure that the polarity is correct: - brown wire to earth - white wire to plus Do not use the other two wires (blue, black) and insulate B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Check for loose or uninsulated wires in the terminal boxes of the pumps, mixing valve and switch valve, which could cause a short-circuit 3.1.3 System check r Check that the main fuse for the boiler has a sufficient rated amperage Ü "Mains connection" [} 8] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Connect Setting parameters required for the boiler to use the “froeling-connect.com” online control (IP address, display password, etc.) Heating up program Activation and selection of a heating up program. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Then the basic screen of the touch display is shown. 1: Selection of the controller language 2: Setting the production number (see identification plate) 3: Setting the date and time 4: Display of the basic screen B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
3: Tap the icon of the settings wizard 4: Tap the “Boiler” setting wizard 5: The settings wizard loads 6: Read the information text and continue with “YES” to start B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 38
Field pump 0-10 V + valve Solar pump 0-10 V + valve Switch valve Ü "Activation options of pump outlets" [} 92] Continue to the next step Go back one step B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Room temperature which is regulated outside of the set heating times. heating times. Flow temperature SP at outside air temperature of +10°C First setting point for definition of heating curve. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If the outside air temperature exceeds this value during heating, the heating circuit pumps and mixing valve are deactivated. 4.1.3 Heating - Times System menu Heating Ü "Setting times" [} 102] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
▪ NO: During DHW tank loading this heating circuit is compensated basis. deactivated. ▪ YES: Despite active DHW tank priority, this heating circuit is supplied with heat during DHW tank loading. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Service Outfeed temperature setpoint on day 1 … 30 If “heating up program 8” is selected, the flow temperature setpoint can be preset for each day using this setting. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 43
If the current room temperature falls below the set frost protection temperature setpoint, this influences the set flow temperature setpoint of the heating up program. NOTE: Only in conjunction with remote control! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
“Desired DHW tank temperature“ has been Specifies the speed of the DHW tank pump as a reached. percentage of maximum speed. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
DHW ▪ YES: If in the current day the DHW tank has already tank temperature + 3°C. been loaded once, any further DHW tank loading is prevented. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
In order to perform the calculation sensor in the lower part of the buffer tank. more precisely, the use of a collector return sensor is recommended. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 47
Collector pump control Indicates which heat sink (buffer tank, DHW tank) is currently being loaded. Display of the current speed of the collector pump as a percentage of maximum speed. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Also when the criteria for starting the collector pump have reached after the set time, the collector pump starts. been reached, the collector pump is only active up to the set time. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If no temperature Pump outlet to which the solar isolating valve is increase on the collector sensor is detected, the collector connected. pump switches off and the time restarts from zero. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Collector temperature Collector return temperature Display of the current temperature at the solar collector. Prerequisite: Hydraulic system 12 or 13 Display of the current temperature at the collector return. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Display of the current temperature in the lower part of the position at the storage tank. All of the configured sensors buffer tank. are used to calculate the storage tank charge status. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Difference, which must be given for loading a buffer tank e.g. in an adjacent building. If this difference is not reached, the buffer tank loading stops. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Sensor input of buffer tank bottom sensor Sensor input to which the sensor in the bottom part of the buffer tank is connected. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
“Boiler off” mode, etc.). 4.5.2 Boiler - Temperatures System menu Boiler Boiler temperature setpoint The boiler temperature is regulated to this temperature. PE1e setting range: 70-90°C B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If there is no option of skimming via the heating circuits or not set value to less than 150s! DHW tank, a pump or a valve can be controlled via the assigned pump outlet to cool the boiler. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
°C. The selected statuses can be cancelled and thus ▪ NO: In conjunction with a data logger, all temperature bypassed. values are saved in °F. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 57
Boiler number By setting the boiler number, this is automatically transferred into the commissioning report when it is saved. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If the secondary boiler is started, it will run for at least the activated immediately on request. length of time set here. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Which pump output is used for unloading the controlled can be adjusted using this parameter. backup boiler Pump outlet to which the loading pump of the backup boiler or the backup boiler switch valve is connected. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If the selected suction point is generally not in use or should not be used due to a problem (suction hose, blockage by pellets, etc.) the suction point can be locked by tapping on this area. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Before switching to the next probe, each probe that was last used is back-flushed for the time set. NOTICE! This parameter is not in use for feed system “3 probe switch”! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 62
System menu Feed system Setting the relevant outputs for the various components. Service - inputs Service Inputs System menu Feed system Setting the relevant inputs for the various components. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
▪ YES: If there are no pellets left in the store, this parameter can be used to disable the discharge system and use firewood for heating instead. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
The return temperature from distributor 1 is regulated to the value set here. When the return temperature from distributor 1 reaches the specified value, the pump for distributor 1 starts up at minimum speed. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Pump outlet to which the pump for distributor 1 is distributor 2 ... 4 installed connected. Adjustment of the minimum speed to the pump type (set mode of pump in accordance with pump manufacturer). B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Display of the signal for the combustion controller. control by means of mixing valve or bypass pump. Displays the current temperature of the boiler return for the backup boiler. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
(% / 10min)] If the storage tank discharge is greater than the set value within 10 minutes, the boiler with the greatest rated heat output will be started (quick start). B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Start priority of slave boiler 3 connection is made. Sensor input of the bottom sensor switch Specifies the input of the bottom sensor switch to which the connection is made. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 69
Delay for the request of the boiler from a flue gas min. temp For a cascade that has no storage tanks, the request for a further boiler / switching off a boiler is subject to a delay. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
4.10.3 Difference regulator - Times System menu Difference regulator Ü "Setting times" [} 102] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
“NO”, 0°C is permanently displayed. ▪ 0: The button is not pressed ▪ 1: The button is pressed Speed of the circulation pump Specifies the current speed of the circulation pump. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Sensor input to which the flow switch is connected. Ü "Activation options of pump outlets" [} 92] If the flow switch is implemented as a push button, connect the external button directly to the sensor input. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
▪ ON: Burn back flap is opened. NOTICE! This parameter can only be activated when the boiler is in “Standby” or “Boiler off” status. Shaker If a sack silo i used, the shaker is manually controlled. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
The parameters displayed depend on the boiler configuration! ▪ A 0: Automatic, Off; A 1-100%: Automatic, with % value ON ▪ 1-100%: Manual, with % value ON ▪ 0%: Manual, Off B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Setting Minimum flue gas temperature Max. flue gas temperature Lowest operation point of flue gas temperature for Highest operation point of flue gas temperature for continuous operation. continuous operation. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 76
100% = spray valve active for the specified time actuated and the calorific value heat exchanger is rinsed. 75% = spray valve active for 15 sec and 5 sec pause B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 77
▪ Status "5": Wait for ready-to-measure state ▪ Excessive temperature HV box ▪ Status "6": Values critical ▪ Error ▪ Status "7": Measure ▪ Restart ▪ Status "8": Measuring mode error B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 78
7 h, the cleaning time of the electrode is only calculated for the 2 h in heating. ▪ NO: The electrode is cleaned only after the boiler has been switched off. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 79
Opening of air flap during pre-heating Desired underpressure which is to be maintained during In “Pre-heating” status, the air flap is opened to this value. the operation of the boiler. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 80
75% = spray valve active for 15 sec and 5 sec pause Condenser heat exchanger cleaning For the indicated period of time, the solenoid valve is actuated and the calorific value heat exchanger is rinsed. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 81
Duration before the vacuum screw delivery system starts. Used to clear the lines before start of suction. Screw cycle The runtime of the delivery screw plus the preliminary suction time equals the screw cycle. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 82
A priority can be assigned in the range 1-3. ▪ 1: Off times for the weekdays and also weekends are active ▪ 2-3: Suction point is always active B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 83
If the current residual oxygen content in “Heating” status Adjustable parameters for the residual oxygen controller. exceeds the specified value, the safety time begins to run. NOTICE! Factory setting - do not change! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 84
Switching-type sensor Lambda values Switching-type sensor Setting Residual oxygen content Lambda probe voltage measured Display of the current residual oxygen content. Display of the current measured Lambda probe voltage. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 85
Ü "Calculating the feed output of the circulating pump" sensors. If an invalid sensor assignment is made, the [} 94] value of the boiler sensor is used to calculate the quantity of heat. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Operation hours System menu System Current values Display of the current number of operation hours of the respective unit and respective components. The parameters displayed depend on the boiler configuration! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Used to delete current faults in the fault list. Depending on the system configuration, the status LED can flash red even though no fault messages are pending. This function can also be used to delete pending fault messages that are not visible. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
This is where you can set the minimum backlight. NOTICE! Once you have changed the module address, you will need to restart the boiler controller (switch main switch on boiler off and on)! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 89
Display settings - Software update / Service Software update / Service System menu Touchscreen Display settings Calibrate screen Restart control Carry out update Ü "Calibrating the touchscreen" [} 104] Ü "Software update Lambdatronic 3200" [} 106] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
If this function is activated, the respective room console is enabled for switching the boiler on and off. In order to be able to operate the boiler, remote switching on the boiler display must also be activated. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
To assign a DHW tank to a specific room console, the respective DHW tank number with its address must set on the room console. The parameters are set to “none” at the factory! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
When set to “Isolating valve” the output is activated either with 0% or 100%. This setting value is only available in the “Water” or “Boiler 2” menu. HKP0 The following applies to pump outlet HKP0 at the core module: ▪ Relay output ▪ Speed control is not possible B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
The FGR ducts are cleaned by a flow of air through appropriate air flap settings and activation of the induced draught fan. Empty stoker The residual material in the stoker screw is burnt. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Boiler with 3-way mixing valve r Set mixing valve to manual operation and turn the lever to the central position r Activate the circulating pump in manual operation with 100% speed B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 95
Activate the circulating pump in manual operation at 50% speed r Press the push bar on the line regulating valve; make a note of the flow on the scale B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 96
Go to the menu “System → Settings → Boiler heat quantity calculation” r Enter the recorded values for the flow of the circulating pump at the respective parameter B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Example 2: "Automatic” mode without storage tank with solar panel system Boiler time 2 Boiler time 1 Heating time 1 Heating time 2 setback mode DHW tank loading time 1 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Example 2: “Automatic” mode with storage tank and solar panel system Storage tank loading time 1 Heating time 2 Heating time 1 setback mode DHW tank loading time 1 DHW tank loading time 2 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
5.5.4 “Continuous load” mode with storage tank To ensure efficient operation, set systems with a storage tank to “Automatic” mode rather than “Continuous load” mode. Ü "“Automatic” mode with storage tank" [} 98] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Tip: In systems with solar panels, choose the DHW tank loading time so that solar energy can be used. Example 2: “Domestic hot water” mode without storage tank with solar panel system DHW tank loading time 1 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Example 2: “Domestic hot water” mode with storage tank and solar panel system Storage tank loading time 1 DHW tank loading time 1 DHW tank loading time 2 B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Tap the symbol under the day of the week Ä The edit window will appear You can specify up to four time windows per component and day. r Tap the desired time window B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 103
If you want to apply the time window setting to another day in addition, you can do this by activating the relevant day. A set time window can be deleted by tapping on the “Recycle bin” symbol. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
In the “Software update / Service" menu open the “Recalibrate touch control” parameter r Set the parameter to “YES” and confirm at the bottom right Ä The touchscreen will restart and begin calibrating B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 105
NOTICE Inaccurate calibration If you do not tap the indicated points accurately, the control may stop working properly and a software update may be required. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
USB-A USB-A Ü "Carrying out a software update on the touch control" [} 109] r Close Flash Update Wizard - restart controller Lambdatronic Service Ü "Finishing a software update" [} 110] B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Ä A window is displayed where you can search for the Flash file r Navigate to the folder where the file is saved r Select the Flash (*.s19) file and click on the "Open" button B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Page 108
When the flash update is successfully transferred to the boiler controller, the following window appears: NOTICE! Do not close the update at this time and do not disconnect the boiler controller! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Once the update is complete, a message will appear that you can remove the stick r Remove the USB stick Ä The touch control restarts automatically The touch control software is up-to-date following the restart. r Perform updates to any other touch controls B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Ä After restarting the boiler controller, check whether all touch controls have started up correctly NOTICE! If not all touch controls connect to the boiler control, a restart of the entire system (main switch OFF/ON) is necessary! B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...
Ä The USB must not contain a software update Ä Recording starts automatically once the touch display has started Data recording is indicated in the status line by means of the USB symbol with an activity bar. B1780023_en | Service handbook Lambdatronic P 3200 - PE1e Pellet 45-60...