Summary of Contents for Fröling Lambdatronic P 3200
Page 1
Service handbook Lambdatronic P 3200 - P4 Pellet Core module version 55.04 - Build 05.21 | Touch control version 60.01 Build 01.39 Translation of original German version of service handbook for technicians. Read and follow all instructions and safety instructions.
4.3.1 Solar - Status ..........................46 4.3.2 Solar - Temperatures ......................... 48 4.3.3 Solar - Times..........................48 4.3.4 Solar - Service ........................... 49 4.3.5 Solar - Heat meter........................50 4.4 Buffer tank............................. 51 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 3
4.14.4 Diagnostics - Clear error history ....................86 4.15 Touchscreen ............................86 4.15.1 Touchscreen - Display settings....................86 4.15.2 Touchscreen - Display operating rights ..................88 4.15.3 Touchscreen - Display allocation ....................89 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 4
5.8.1 Carrying out a software update on the boiler controller ............. 104 5.8.2 Carrying out a software update on the touch control ..............106 5.8.3 Finishing a software update ....................... 107 5.9 USB data recording..........................108 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Insulate the flue gas pipes and do not touch them during operation The information on safety, standards and guidelines in the assembly and operating instructions for the boiler should also be observed! B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Null modem cable 9-pin SUB-D; Connection is used e.g. as MODBUS interface KM-05 COM 1 Null modem cable 9-pin SUB-D; Service interface for software updates and connection to visualisation software B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 7
3 x 1.5 mm , max. 2A or burner relay KM-35 Operating signal Connection cable 2 x 0.75 mm Ü "Operating signal" [} 15] 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
In the delivered state, the outside temperature sensor is read in by the core module ("KM-19 / outside temperature sensor" connection). Alternatively, the outside temperature sensor can be connected to an additional heating circuit module. Ü "Heating circuit module" [} 16] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Handwheel… Allows you to adjust the temperature by +/- 3°C IMPORTANT! Refer to the supplied assembly instructions for more detailed explanations on connecting and operating the FRA room temperature sensor. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
The speed of HCP 0 is not controlled. (Observe the pump dimensions!) r Setting the “Continuous load” mode The higher level control system should ensure a minimum activation time of 15 minutes for the pellet boiler. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r Set control of the pump in the relevant menu to “Field pump / PWM” or “Field pump / 0-10V” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 12
Please note that the minimum speed may need to be adjusted on some pumps (default setting: 30%). FRKEM29 AO-P1 r Connect pump to output “Pump 1” of the core module r In the relevant menu, set the pump control to “Pump without control signal” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r In the relevant menu, set the activation of the pump to “Field pump PDM + valve” or to “Field pump 0-10V + valve” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 14
Connect the phase (L) for switching over the valves together with the phase (L) for the pump to the switched output of the relay r In the relevant menu, set the pump control to “HE pump without control signal” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
4 x 0.75 mm , max. 0.15A / 230V HE-12 Mixing valve 2 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 Fuses 6.3 AT HE-09, HE-10, HE-11, HE-12 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Depending on the type of pump, the phase (L) is either connected to the relay output or triac output. Connecting a circulating pump to the hydraulic module 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 18
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r Set control of the pump in the relevant menu to “Field pump / PWM” or “Field pump / 0-10V” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 19
Connect the power supply for the pump to output “Pump 1” or “Pump 2” and use the triac output for phase r In the relevant menu, set the pump to “Pump without control signal” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 20
) from NOC on the relay to the pump using terminal “S/S” as the release contact r Connect power supply at pump connector r In relevant menu, set pump to “Field pump PDM + valve” or “Field pump 0-10V + valve” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 21
Ä Make sure that the cables are configured correctly (polarity) in accordance with the connection diagram of the pump! r In the relevant menu, set the activation of the pump to “Field pump PDM + valve” or to “Field pump 0-10V + valve” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 22
Phase (L) for switching the valve and connecting neutral conductor (N) to output “Pump 1” or “Pump 2” using the relay output for phase (L) r Connect the phase (L) for continuous supply (switches the valve back to the initial position) to the power supply at terminal “L” B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
3 x 1.5 mm , max. 4A / 230V / 900W PE-09 Pellet module Ribbon cable to connect to pellet module 1. YMM to ÖVE-K41-5 or H05VV-F to DIN VDE 0881-5 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 26
NOTICE! The return signal of the room air flap at input “Digi IN” must have a floating design. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
NOTICE! The inputs and output are pre-configured, so it is essential the following addressing is complied with. Standard configuration – Analogue module with address 0 Input Designation External power specification (0-10V) B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 28
(“Boiler release input available” parameter = YES). Necessary parameters for setting the power demand can be found in the “Boiler – General settings” menu. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
For the bus connections between the individual modules, cable type LIYCY paired 2x2x0.5 should be used. The connection to the 5-pin plugs should be carried out according to the following diagram: Braided shield Braided shield white white green green yellow yellow brown brown B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
If the contacts at the base of the end jumper are not bridged (image left), it is referred to as “not set". In this case there is no bus termination. If the contacts are closed (image right), the end jumper is set and the bus connection is terminated. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Instead of the potential equalisation, a Fröling bus repeater can be used in the bus connection line to the next building. The potential separation (galvanic isolation) allows the bus network to be split into two separate sub- networks. Bus side A Bus side B Expansion Bus repeater module B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Connect the control cable to the PDM output on the board, making sure that the polarity is correct: - brown wire to earth - white wire to plus Do not use the other two wires (blue, black) and insulate B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Check for loose or uninsulated wires in the terminal boxes of the pumps, mixing valve and switch valve, which could cause a short-circuit 3.1.3 System check r Check that the main fuse for the boiler has a sufficient rated amperage Ü "Mains connection" [} 8] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Connect Setting parameters required for the boiler to use the “froeling-connect.com” online control (IP address, display password, etc.) Heating up program Activation and selection of a heating up program. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Then the basic screen of the touch display is shown. 1: Selection of the controller language 2: Setting the production number (see identification plate) 3: Setting the date and time 4: Display of the basic screen B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
3: Tap the icon of the settings wizard 4: Tap the “Boiler” setting wizard 5: The settings wizard loads 6: Read the information text and continue with “YES” to start B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 38
Field pump 0-10 V + valve Solar pump 0-10 V + valve Switch valve Ü "Activation options of pump outlets" [} 90] Continue to the next step Go back one step B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Room temperature which is regulated outside of the set heating times. heating times. Flow temperature SP at outside air temperature of +10°C First setting point for definition of heating curve. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
If the outside air temperature exceeds this value during heating, the heating circuit pumps and mixing valve are deactivated. 4.1.3 Heating - Times System menu Heating Ü "Setting times" [} 99] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
If time has run out, the heating circuit will go back to being supplied on a weather- compensated basis. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Heating up program Service Outfeed temperature setpoint on day 1 … 30 If “heating up program 8” is selected, the flow temperature setpoint can be preset for each day using this setting. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 43
If the current room temperature falls below the set frost protection temperature setpoint, this influences the set flow temperature setpoint of the heating up program. NOTE: Only in conjunction with remote control! B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
DHW tank pump control window has elapsed or the temperature set under “Desired DHW tank temperature“ has been Specifies the speed of the DHW tank pump as a reached. percentage of maximum speed. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
DHW ▪ YES: If in the current day the DHW tank has already tank temperature + 3°C. been loaded once, any further DHW tank loading is prevented. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Display of the current temperature at the solar reference transmitter is used. In order to perform the calculation sensor in the lower part of the buffer tank. more precisely, the use of a collector return sensor is recommended. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 47
Collector pump control Indicates which heat sink (buffer tank, DHW tank) is currently being loaded. Display of the current speed of the collector pump as a percentage of maximum speed. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Also when the criteria for starting the collector pump have reached after the set time, the collector pump starts. been reached, the collector pump is only active up to the set time. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
If no temperature Pump outlet to which the solar isolating valve is increase on the collector sensor is detected, the collector connected. pump switches off and the time restarts from zero. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Solar Collector temperature Collector return temperature Display of the current temperature at the solar collector. Prerequisite: Hydraulic system 12 or 13 Display of the current temperature at the collector return. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Display of the current temperature in the lower part of the position at the storage tank. All of the configured sensors buffer tank. are used to calculate the storage tank charge status. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Difference, which must be given for loading a buffer tank e.g. in an adjacent building. If this difference is not reached, the buffer tank loading stops. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Sensor input of buffer tank bottom sensor Sensor input to which the sensor in the bottom part of the buffer tank is connected. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
▪ 1: A heating circuit or DHW tank requires heat. The start criterion must be fulfilled for a boiler start (e.g. boiler times active, boiler is not in “Boiler off” mode, etc.). B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
The boiler setpoint temperature in heating mode is (prevention of cold through flow!). increased by this value compared to the required flow temperature. 4.5.3 Boiler - Times System menu Boiler Ü "Setting times" [} 99] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
▪ Celsius (°C): Displayed temperature values and ▪ YES: The boiler has a modem for data transfer settings are shown in °C. installed. ▪ Fahrenheit (°F): Displayed temperature values and settings are shown in °F. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 57
MODBUS protocol (1 – RTU / 2 – ASCII) Indicates which Modbus protocol is to be used for the transfer. Which protocol must be used can be found in the documentation of the Modbus system used on site. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Indicates the current status of the control process of the Standby boiler switch valve heat pump. Prerequisite: Set the parameter “Switch valve installed“ to “YES” Display of the current switch valve control of the standby boiler. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
After the set time the valves switches back to the main boiler. This allows the backup boiler it has a certain period during which it can be warmed up after it was shut down. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
▪ A: Standby boiler is controlled according to the program that is set. ▪ 1: Standby boiler was started manually. ▪ 0: Backup boiler was stopped manually. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
If the selected suction point is generally not in use or should not be used due to a problem (suction hose, blockage by pellets, etc.) the suction point can be locked by tapping on this area. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Minimum path for gate valve This value is automatically set to 5% below the measured path of the gate valve after its initial startup. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
▪ YES: The “resettable t-counter” and also the start-up or after a software update to software “version “resettable kg-counter” is set to “0”. 50.04 – Build 05.09” or higher, the counter is automatically activated. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Speed, distributor 2 ...4 pump Prerequisite: Variant 2 or variant 3 and pump for distributor 2 ... 4 installed Display of the current speed of the distributor 2 … 4 pump. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Control of network pump Pump outlet to which the pump for distributor 1 is Definition of control signal for pump type used. connected. Ü "Activation options of pump outlets" [} 90] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
System menu Cascade Slave boiler boiler temperature Slave boiler OK Display of the current boiler temperature of the backup Display of whether the backup boiler is ready for boiler. operation. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Start point 2 at storage tank charge If the storage tank charge is lower than this value, the second boiler is started. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 68
When the storage tank charge exceeds the value which is set under “Start point 1 at storage tank charge”, the boiler control variable for the boilers that are still active will be reduced using the boiler loading pump. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Start priority of slave boiler 3 connection is made. Sensor input of the bottom sensor switch Specifies the input of the bottom sensor switch to which the connection is made. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 70
Delay for the request of the boiler from a flue gas min. temp For a cascade that has no storage tanks, the request for a further boiler / switching off a boiler is subject to a delay. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
4.10.3 Difference regulator - Times System menu Difference regulator Ü "Setting times" [} 99] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
“NO”, 0°C is permanently displayed. ▪ 0: The button is not pressed ▪ 1: The button is pressed Speed of the circulation pump Specifies the current speed of the circulation pump. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Sensor input to which the flow switch is connected. Ü "Activation options of pump outlets" [} 90] If the flow switch is implemented as a push button, connect the external button directly to the sensor input. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
▪ ON: The hot air blower / ignition rod for igniting the fuel is activated. exchanger is cleaned. NOTICE! This parameter can only be activated when the boiler is in “Standby” or “Boiler off” status. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
The parameters displayed depend on the boiler configuration! ▪ A 0: Automatic, Off; A 1-100%: Automatic, with % value ON ▪ 1-100%: Manual, with % value ON ▪ 0%: Manual, Off B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
System Setting Minimum flue gas temperature Max. flue gas temperature Lowest operation point of flue gas temperature for Highest operation point of flue gas temperature for continuous operation. continuous operation. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 77
Condenser heat exchanger cleaning available from Time from which the washing process can be activated. Condenser heat exchanger cleaning available until Time to which the washing process can be activated. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 78
ID fan is calculated. ID fan during shutdown In “Shutdown” status, the induced draught blower fan is operated with the specified control. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 79
85%. If you only want one filling time, then set the second filling time to the same time as the first filling time. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 80
Prerequisite: Universal suction with automatic toggle Shaker timing The default vibration interval timing is 60%: Time basis: 100 sec. → 60 sec. on / 40 sec. pause B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 81
Minimum air speed which must be reached in specified time. “Preparation” status to perform a start-up. Setting - Lambda probe Lambda probe System menu System Setting Residual oxygen content Display of the current residual oxygen content. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 82
Lambda probe voltage measured Display of the current measured Lambda probe voltage. Lambda probe voltage corrected Display of the measured Lambda probe voltage, at which the „Lambda probe correction value“ governs the response. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 83
Flow rate at 100% pump rotation speed The parameter specifies the volumetric flow rate at 100% pump actuation. Ü "Calculating the feed output of the circulating pump" [} 92] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Sensors and pumps In the “Sensors and pumps” menu, all sensor inputs and pump outlets available in the hydraulic system can be allocated. The number of parameters depends on the configuration. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
(cleared). If all 50 fault indication entries are in use and there is another fault indication entry, the oldest entry will be deleted to make room for the current one. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
▪ On: The address in the local network (IP address), the subnet mask, default gateway and DNS server are automatically assigned by the router/server. ▪ Off: IP address, subnet mask, default gateway and DNS server can be manually set. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 87
(e.g. when replacing the core Ü "Software update Lambdatronic 3200" [} 103] module). Restart display Touch control unit is restarted and the data is reloaded from the core module. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
If this function is activated, the respective room console is enabled for switching the boiler on and off. In order to be able to operate the boiler, remote switching on the boiler display must also be activated. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
To assign a DHW tank to a specific room console, the respective DHW tank number with its address must set on the room console. The parameters are set to “none” at the factory! B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
When set to “Isolating valve” the output is activated either with 0% or 100%. This setting value is only available in the “Water” or “Boiler 2” menu. HKP0 The following applies to pump outlet HKP0 at the core module: ▪ Relay output ▪ Speed control is not possible B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
The Lambdatronic controls the connected heating components. The boiler waits for a start request from the hydraulic system. Boiler off The boiler controller controls the connected heating components. All parts of the boiler are deactivated. Chamber discharge system active! B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Activate the circulating pump in manual operation at 50% speed r Press the push bar on the line regulating valve; make a note of the flow on the scale B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 93
Configuring the heat quantity calculation r Go to the menu “System → Settings → Boiler heat quantity calculation” r Enter the recorded values for the flow of the circulating pump at the respective parameter B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Example 2: "Automatic” mode without storage tank with solar panel system Boiler time 2 Boiler time 1 Heating time 1 Heating time 2 setback mode DHW tank loading time 1 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Example 2: “Automatic” mode with storage tank and solar panel system Storage tank loading time 1 Heating time 2 Heating time 1 setback mode DHW tank loading time 1 DHW tank loading time 2 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
5.5.4 “Continuous load” mode with storage tank To ensure efficient operation, set systems with a storage tank to “Automatic” mode rather than “Continuous load” mode. Ü "“Automatic” mode with storage tank" [} 95] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Tip: In systems with solar panels, choose the DHW tank loading time so that solar energy can be used. Example 2: “Domestic hot water” mode without storage tank with solar panel system DHW tank loading time 1 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Example 2: “Domestic hot water” mode with storage tank and solar panel system Storage tank loading time 1 DHW tank loading time 1 DHW tank loading time 2 B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Tap the symbol under the day of the week Ä The edit window will appear You can specify up to four time windows per component and day. r Tap the desired time window B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 100
If you want to apply the time window setting to another day in addition, you can do this by activating the relevant day. A set time window can be deleted by tapping on the “Recycle bin” symbol. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
In the “Software update / Service" menu open the “Recalibrate touch control” parameter r Set the parameter to “YES” and confirm at the bottom right Ä The touchscreen will restart and begin calibrating B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 102
NOTICE Inaccurate calibration If you do not tap the indicated points accurately, the control may stop working properly and a software update may be required. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
USB-C USB-A USB-A Ü "Carrying out a software update on the touch control" [} 106] r Close Flash Update Wizard - restart controller Lambdatronic Service Ü "Finishing a software update" [} 107] B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Ä A window is displayed where you can search for the Flash file r Navigate to the folder where the file is saved r Select the Flash (*.s19) file and click on the "Open" button B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 105
When the flash update is successfully transferred to the boiler controller, the following window appears: NOTICE! Do not close the update at this time and do not disconnect the boiler controller! B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Once the update is complete, a message will appear that you can remove the stick r Remove the USB stick Ä The touch control restarts automatically The touch control software is up-to-date following the restart. r Perform updates to any other touch controls B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Ä After restarting the boiler controller, check whether all touch controls have started up correctly NOTICE! If not all touch controls connect to the boiler control, a restart of the entire system (main switch OFF/ON) is necessary! B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Ä The USB must not contain a software update Ä Recording starts automatically once the touch display has started Data recording is indicated in the status line by means of the USB symbol with an activity bar. B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 109
Notes B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...
Page 110
B1790023_en | Service handbook Lambdatronic P 3200 - P4 Pellet...