Omega PHCN-961 User Manual

Omega PHCN-961 User Manual

Ph/orp controller

Advertisement

Quick Links

User' s Guide
Shop online at
omega.com
e-mail: info@omega.com
For latest product manuals:
omegamanual.info
MADE IN TAIWAN
PHCN-961
pH/ORP Controller

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PHCN-961 and is the answer not in the manual?

Questions and answers

Summary of Contents for Omega PHCN-961

  • Page 1 User’ s Guide Shop online at omega.com e-mail: info@omega.com For latest product manuals: omegamanual.info MADE IN TAIWAN PHCN-961 pH/ORP Controller...
  • Page 2 Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification. The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
  • Page 3 Preface - This manual serves to explain the use of PHCN-961 series controller / transmitter. This instruction manual is written to cover as many anticipated applications of PHCN-961 series controller / transmitter. The information presented in this manual is subject to change without notice as...
  • Page 4 ___________ ____________________________ SAFETY INFORMATION OMEGA ENGINEERING. Controller / Transmitter shall be installed and operated only in the manner specified in the Instruction manual. Only skilled, trained or authorized person should carry out installation, setup and operation of the instrument. Before powering up the unit, make sure that power source is connected to, is as specified in the top label.
  • Page 5: Table Of Contents

    2.3.3 LED INDUCTION 2.3.4 PASSWORD 2.3.5 PREVIEW OF FUNCTION 3 INSTALLATION AND ACCESSORY INSTALLATION PHCN-961 CONNECTION DIAGRAM MEASUREMENT MODE 4 CALIBRATION MODE ENTERING CALIBRATION MODE pH CALIBRATION ORP–mV CALIBRATION 5 SET UP MODE ENTERING SET UP MODE P01_TEMPERATURE SET-UP SUB-FUNCTION...
  • Page 6 ___________ ____________________________ P09_TRANSMITTING RATE SUB FUNCTION 5.10 P10_REVERTING TO FACTORY DEFAULT SETTINGS 5.11 COMMUNICATION PROTOCOL 6 TECHNICAL PARAMETERS TECHNICAL PARAMETERS FORM PARAMETER SETTING AND FACTORY PRELIMINARY VALUE APPENCLIX 2 – pH TEMPERATURE CORRESPONDING TO pH BUFFER SOLUTION APPENCLIX 3 – HYSTERESIS BAND APPENCLIX 4 –...
  • Page 7: Preface

    If they are neglected, it will cause low efficient and even losing products. Instruction manual should be kept accessible to the person who will use the use pH/ORP controller/ transmitter. If you have problems, which are not mentioned in this manual, please contact Omega Engineering. IN USE OMEGA ENGINEERING .
  • Page 8: Safety Instruction

    ___________ ____________________________ SAFETY INSTRUCTION pH / ORP transmitters should be installed and operated by qualified person. Transmitters with problems should not be installed and/or used. pH / ORP transmitters should be used under acceptable working conditions. pH / ORP transmitters should not be open and repaired by clients them selves.
  • Page 9: Product Description

    2 PRODUCT DESCRIPTION 2.1 DESCRIPTION OF INSTRUMENT SPECIALITY: OMEGA ENGINEERING . pH / ORP transmitters are used to measure pH or ORP and temperature value. This transmitter has many user-friendly and safety features which include: • Menu-driven programs that are easy to set-up.
  • Page 10: Measurement And Control System

    ___________ ____________________________ 2.2 MEASUREMENT AND CONTROL SYSTEM Typical measurement system includes: • pH/ORP on-line transmitter • Intergral or separated temperature sensor (Pt1000). • Suitable pH/ORP measurement electric cable. • Immersion, flow or processing parts with or without grounding electrode. • Terminating controlling parts, eg.
  • Page 11: Appearance

    APPEARANCE panel installation PHCN-961...
  • Page 12: Introduction Of Display

    ___________ ____________________________ 2.3.1 INTRODUCTION OF DISPLAY Two liquid crystal regions show measured value and indication and parameters of various status. CAL SET Mode Indication_ 7.00 – MEA : measurement mode – SET : set-up mode – CAL : calibration mode Status Indication: HOLD : –...
  • Page 13: Key Instruction

    2.3.2 KEY INSTRUCTION Description • Mode switch key or quit key • Confirm key • Entering sub-function form of function group in setting mode • Confirm setting parameter and value • Starting calibrating in calibration mode • Back light on and off switch in measurement mode •...
  • Page 14: Preview Of Function

    ___________ ____________________________ 2.3.5 PREVIEW OF FUNCTION 7.00 I2.00 25.0 HOLD P02: OFFSET SETUP HOLD HOLD HOLD HOLD P04: CONTROL MODE HOLD HOLD P05: RELAY1 SETUP P06: RELAY2 SETUP HOLD P07: ALARM RELAY HOLD SETUP P08: CONFIG SETUP HOLD HOLD HOLD HOLD P09: RS-485 SETUP HOLD...
  • Page 15: Installation And Accessory

    3 INSTALLATION AND ACCESSORY INSTALLATION 136(5.35) 12(0.47) 1-7(0.03-0.27 100(3.93) 93.5(3.68) 108(4.25) 93.5(3.68) Panel cutout:93.5 * 93.5mm (panel installation)
  • Page 16: Phcn-961 Connection Diagram

    ___________ ____________________________ connection diagram PHCN-961 Warning : Make sure to power off before connecting. The back panel consists of three connectors. PHCN-961 series connection diagram pH/ORP INPUT 485A 485B 13 14 15 16 NEW VERSION NEW VERSION 1. pH value 4—20mA output, positive terminal 14.
  • Page 17: Measurement Mode

    MEASUREMENT MODE When the controller is initially powered on, it automatically enters into the Measurement mode after the large dual LCD displays all segments briefly. Please notice: in order to get exact measurement information, users should calibrate measurement system (transmitter and electrode). MEA at the top of the LCD shows that the instrument is 7.00 under the status of measuring.
  • Page 18: Calibration Mode

    ___________ ____________________________ 4 CALIBRATION MODE You can press once under measurement mode and then input password 28 to get access to calibration mode. Please operate according to following: ENTERING CALIBRATION MODE S E T C A L C A L S E T 7.00 H O L D...
  • Page 19: Ph Calibration

    pH CALIBRATION This instrument can conduct one point or two points calibration in pre-set standard buffer liquid. The value of standard buffer solution is based on 25°C. Entering calibration mode as Item 4.1 described. LCD will show CAL pH. (pH Calibration mode).
  • Page 20 ___________ ____________________________ Press twice to quit one-point calibration and return to measuring status. Press to continue next point calibration. Take electrode out of the first standard solution, clean it and put it into the second standard solution. If one point calibration is selected, instrument will show the slope, but zero point adopts new calibration value while the slope remains the value of last calibration.
  • Page 21 NOTE: Press key to quit set up mode at any time. Instrument will return to measurement mode automatically. NOTE: Transmitter will show ERR when calibration is in error. Under this situation, press to quit and calibrate again from step 1. It will show ERR again under following situations: (1) Use wrong standard solution or standard solution is expired.
  • Page 22: Orp-Mv Calibration

    ___________ ____________________________ ORP CALIBRATION If transmitter is set up as ORP measurement mode. You can only calibrate one point. C A L C A L S E T S E T H O L D H O L D S P I S P 2 4.00 C A L...
  • Page 23: Set Up Mode

    5 SET UP MODE ENTERING SET UP MODE In set up mode, transmitter can be set up according to your need. S E T S E T S E T 7.00 A T C S P I S P 2 I2.00 25.0 Press twice in measurement mode.
  • Page 24: P01_Temperature Set-Up Sub-Function

    ___________ ____________________________ P01: TEMPERATURE SET-UP SUB-FUNCTION 7.00 HOLD HOLD HOLD HOLD HOLD done I2.00 25.0 7.00 HOLD HOLD HOLD done I2.00 25.0 Press to enter from P01 screen. LCD main display zone shows ON, which means automatic temperature compensation function, is on. User can press to switch to OFF and stop automatic temperature compensation function.
  • Page 25: P02_Offset Set-Up Sub-Function

    P02: OFFSET SET-UP SUB-FUNCTION HOLD HOLD 7.00 HOLD HOLD 07.00 I2.00 25.0 done 1.In P02 sub-function form, Press . LCD main display zone shows pH actually measured value in pH measurement mode. The lower display shows POFS. The right lower display show offset.
  • Page 26: P03: Output Electric Circuit_Sp1/Sp2_ Sub-Function

    ___________ ____________________________ P03: OUTPUT ELECTRIC CIRCUIT (SP1/SP2) SUB-FUNCTION 7.00 HOLD HOLD HOLD HOLD HOLD done I2.00 25.0 HOLD 7.00 HOLD HOLD HOLD done I2.00 25.0 Press to confirm in P03 sub-function. Entering set up of the sub-function. The lower display shows CTYP. The upper display shows 4 (it means electric circuit output from 4 m A to 20 m A).
  • Page 27: P04_Control Mode Sub-Function

    P04: CONTROL MODE SUB-FUNCTION 7.00 HOLD HOLD HOLD I2.00 25.0 done 7.00 HOLD HOLD done I2.00 25.0 Press in P04 sub-function form to enter into set up procedure. The lower display shows CNTR while the upper display shows LIT. (The control mode of instrument is under limited control mode).
  • Page 28: P05_Relay 1 Set-Up Sub-Function

    ___________ ____________________________ P05: RELAY 1 SET-UP SUB-FUNCTION HOLD 7.00 HOLD HOLD HOLD done I2.00 25.0 7.00 HOLD HOLD HOLD HOLD HOLD HOLD done I2.00 25.0 7.00 HOLD HOLD HOLD HOLD HOLD done I2.00 25.0 7.00 HOLD HOLD HOLD HOLD HOLD HOLD done I2.00 25.0...
  • Page 29: P06_Relay 2 Set-Up Sub-Function

    P06: RELAY 2 SET-UP SUB-FUNCTION Working principle of this part is the same as which of P05 relay 1 set-up sub-function. Please operate according to P05. I0.00 7.00 HOLD HOLD HOLD HOLD done I2.00 25.0 I0.00 HOLD HOLD 7.00 HOLD HOLD HOLD done...
  • Page 30: P07_Alarm Relay 3 Set-Up Sub-Function

    ___________ ____________________________ P07: ALARM RELAY 3 SET-UP SUB-FUNCTION HOLD HOLD 7.00 HOLD HOLD done I2.00 25.0 HOLD HOLD HOLD HOLD 7.00 done I2.00 25.0 HOLD HOLD HOLD HOLD 7.00 done I2.00 25.0 Select P07 sub function, Press to confirm. Enter into set-up procedure. Select working mode.
  • Page 31: P08_Ph/Orp And Sensor Configuration Sub-Function

    P08: pH/ORP function AND SENSOR CONFIGURATION sub-function HOLD HOLD SENS HOLD HOLD HOLD HOLD HOLD 7.00 HOLD FUNC done I2.00 25.0 HOLD HOLD HOLD SENS HOLD HOLD FUNC HOLD FUNC In P08, Press to confirm and enter into set up procedure. Press to confirm.
  • Page 32: P09_Transmitting Rate Sub Function

    ___________ ____________________________ P09: transmitting rate sub function HOLD HOLD 7.00 HOLD HOLD HOLD done I2.00 25.0 1. Press to confirm in P09 and enter in set-up procedures. 2. The lower display shows nb while the upper display shows 001, which indicates that user is setting communication address ID NO.
  • Page 33: P10_Reverting To Factory Default Settings

    5.10 P10: reverting to factory default settings HOLD HOLD 7.00 HOLD done I2.00 25.0 HOLD HOLD 7.00 done I2.00 25.0 Press in P10 to enter into set-up procedures. The lower display of the instrument shows DEF while the upper display shows NO (YES). User can press to select necessary items.
  • Page 34: Communication Protocol

    ___________ ____________________________ 5.11 COMMUNICATION PROTOCOL 1. Protocol setting This instrument uses RS-485 communication. It’s can be connected with 1 to 64 instruments in 2 wires at the same time and communicate with PC. The distance of communication is around 1200M. The data form is “N81”(1 start bit, 8 data bits,1 stop bit, NO verify check code) The baud rate is 300 to 38400 bit/s (usually is 9600 bit/s) Users have to set the ID(NB) of the instruments and the baud rate(BT) before connecting to...
  • Page 35 3. The communication instructions 1_ RD: read floating data 2_ RE: read the appointment data by start address and bytes (the large byte can not over 28 bytes) 3_ RR: read all of data (8-word, 12-byte), totally 28 bytes. 4. Introduce the instructions( the ID is 1) 1_ RD (read the floating data): PC send: 40,30,31,51,44,CRCH,CRCL,0D (8 bytes) 40: start byte 30 31: the ID of instrument (the hexadecimal: 0~3FH, ASCII: 30 30~33 46)
  • Page 36 ___________ ____________________________ RE (read the appointment data) The PC send : 40, 30, 31, 52,45, 30, 30, adrH,adrL, lthH, lthL, CRCH, CRCL, 0D (total 14 bytes) 40 : the start byte 30 31 : the ID of instrument (the hexadecimal: 0~3FH, ASCII): 30 30~33 46) : 52 45 : the instruction R, E;...
  • Page 37 The instrument response : 40,30,31,52,52,D1_D2,………,D55_D56,CRCH,CRCL,0D(64 bytes) 40 : the start byte 30 31:ID 52 52 : the fix data D1_D56_the parameter of sending (8 double byte,12 byte, total 28 bytes) CRCH_CRCL: CRC 0D: the end byte 4. Notice for programming the communication program If the instrument receives the data with the start byte is 40 and the count of sequence data over 16 bytes and did not find the 0D then the data is invalid.
  • Page 38: Technical Parameters

    ___________ ____________________________ 6 TECHNICAL PARAMETERS TECHNICAL PARAMETERS FORM PHCN-961 Transmitter / Controller pH Range -2.00 to 16.00 pH Analytical degree & precision 0.01 pH and ± 0.01 pH mV Range -1999 to1999 mV Analytical degree & precision 1 mV / ± 1 mV Temperature -9.9 to 130...
  • Page 39: Parameter Setting And Factory Preliminary Value

    PARAMETER SETTING AND FACTORY PRELIMINARY VALUE Indication Parameter Symbol Contents Remark Valid range Factor Name y value LOCK Password for entering function 0~200 Auto temperature compensation ON/OFF TSET1 tSt1 Temperature set up of manual Only valid for manual -10.0~100.0°C 25.0 TSET2 tSt2 Calibration temperature set up...
  • Page 40: Appenclix 2 - Ph Temperature Corresponding To Ph Buffer Solution

    ___________ ____________________________ APPENCLIX 2 – pH TEMPERATURE CORRESPONDING TO pH BUFFER SOLUTION Following form shows standard pH value of pH standard buffer solution under different temperature Temperature pH 1.00 pH 4.01 pH 6.86 pH 7.00 pH 9.00 pH 9.18 pH 10.01 0.96 4.01 6.98...
  • Page 41: Appenclix 3 - Hysteresis Band

    Appenclix 3 – hysteresis band Simple Explanation on the Function of Hysteresis Band SP1 Set to LO SP2 Set to HI RELAY ON RELAY OFF 10.0 FORWARD DIRECTION HYSTERESIS BAND REVERSE DIRECTION (DEFAULT = 0.5 pH) The controller relay activates when the set-point is reached. In the reverse direction, it closes.
  • Page 42: Appenclix 4 - Control Movement

    ___________ ____________________________ APPENCLIX 4 – CONTROL MOVEMENT General Instructions Concerning Controller Setting MIN Function MAX Function 100 % 50 % + Xw - Xw Prop. Band Prop. Band SP 1 SP 2 Control characteristic of P-Controller as proportional controller MAX Function MIN Function 100 % 50 %...
  • Page 43 Control signal of pulse length control Relay Pulse Length T Time [s] Control signal and pulse length control Out put of relay controlled by hysteresis band is time. Crile T for open or close is constant. Different value comes from limited value, increase or decrease of open time is in accordance with proportion range. Following applications_ = T (Const.) greater divergence ...
  • Page 44: Accessory 5 - Abbreviations In Function Form

    ___________ ____________________________ ACCESSORY 5 – ABBREVIATIONS IN FUNCTION FORM Character Meaning Measurement mode Calibration mode Confirm Zero point offset Set up Automatic temperature cor Set point 1 Set point 2 Low limit High limit CNtr Control Limited point control Pulse length control Relay Output signal CONF...
  • Page 45 CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans.
  • Page 46 Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course! Shop online at omega.com TEMPERATURE Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies Wire: Thermocouple, RTD & Thermistor Calibrators & Ice Point References Recorders, Controllers & Process Monitors...