Installation, Operation and Maintenance instruction
FG / K AC & EC Centrifugal Inline Fan
Inline Duct Fan with Metal Casing
FG 4, 5, 6, and FG EC ONLY
FG 4, 5, 6, et FG EC SEULEMENT
FG 4, 5, 6, y FG EC SOLAMENTE
EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the fantech FG / K AC Series and is the answer not in the manual?

Questions and answers

Summary of Contents for SystemAir fantech FG / K AC Series

  • Page 1 Installation, Operation and Maintenance instruction FG / K AC & EC Centrifugal Inline Fan Inline Duct Fan with Metal Casing FG 4, 5, 6, and FG EC ONLY FG 4, 5, 6, et FG EC SEULEMENT FG 4, 5, 6, y FG EC SOLAMENTE...
  • Page 2: Table Of Contents

    Table of contents 1 Introduction ............1 Product Description........1 Intended Use ..........1 Document Description ........1 Fantech Warranty ........1 Product Overview ........1 Nameplate ..........2 1.6.1 Type Designation ......2 2 Safety ..............2 Safety definitions ......... 2 Safety Instructions ........
  • Page 3: Introduction

    Speak to Fantech for more information on how to install the Introduction product in different installation locations. Product Description Fantech Warranty This product is a circular duct fan with an airtight casing made from sheet metal. The product is not supplied with a wall switch or FC mounting clamps, these parts are available and recommended as accessories.
  • Page 4: Nameplate

    Mounting bracket (for FG / K 6M, #40466, FG / K 6XL, Mounting bracket (for FG / K 12XL, #40413 and FG / K #40407, FG / K 8, #40408, FG / K 8XL, #40409, FG / K 12XL EC, #49905 products) 10, #40410, FG / K 10XL, #40411, FG / K 6M EC, Self-tapping Screws, quantity 2 —...
  • Page 5: Safety Instructions

    • When cutting or drilling into walls or ceilings, watch for Caution electrical wiring and other hidden utilities to prevent damage. If you do not obey these instructions, there is a risk of damage to the product, • Some products are factory wired with a power cord. To other materials or the adjacent area.
  • Page 6: Installation

    Installation To Do Before the Installation of the Product Warning For installations with a range hood, use only metal duct to decrease the risk of a 135° 135° fire. 45° 45° Warning TO REDUCE THE RISK OF A RANGE Note: TOP GREASE FIRE, OBSERVE THE Install the product correctly in relation to the airflow.
  • Page 7 Exhaust Grille Conditioned Air Port Ceiling FG / K AC Series or FG / K EC Series Duct Duct FG / K AC Series or FG / K EC Series Ceiling Exterior Exhaust Air Port Supply Grille Exhaust Grille Conditioned Air Port Reducer FG / K AC Series or FG / K EC Series Duct...
  • Page 8: To Do Before The Installation Of The Duct Run

    Using the marks for guidance, with a 13/64" (5mm) drill To Do Before the Installation bit, make the necessary quantity of pilot holes in the sup- of the Duct Run port beam. Install the necessary quantity of 3/4” (19mm) wood Caution screws into the support beam.
  • Page 9 Note: Note: For FG / K 6, #40406 & #40406A products For FG / K 12XL, #40413 and FG / K 12XL EC, #49905 products Note: Note: For FG / K 6M, #40466, FG / K 6XL, #40407, FG / K 8, #40408, FG / K 8XL, #40409, FG / K 10, #40410, FG / K Installation example of a FG / K AC Series or a FG / K EC 10XL, #40411, FG / K 6M EC, #49900, FG / K 8 EC,...
  • Page 10: To Attach The Duct Without Mounting Clamps

    If you install the product near a duct bend, do these steps to prevent vibrations, unwanted noise, and de- creased air pressure: Measure the distance (A) between the product and the duct bend. Make sure that the distance (A) is a minimum of 2.5 x the diameter (B) of the duct system.
  • Page 11: Electrical Connection

    Electrical connection Operation To connect the product to the Caution power supply EC motors must be set to ON/OFF via the control input. To stop the product via • Make sure that the electrical connection agrees with the mains supply decreases the life time of product specification on the motor name plate.
  • Page 12: Commissioning

    Commissioning Caution • If strong vibrations occur during commissioning, immediately increase or decrease the fan speed until the vibrations are decreased. Continuous strong vibrations can cause damage to components. • Do not increase the fan speed to a higher rpm value than the maximum value that is given on the name plate.
  • Page 13: Maintenance

    Maintenance Warning Set the installed switch(es) in the OFF position before you do the maintenance unless the instructions tell you differently. Make sure that the switch(es) is not accidentally set in the ON position. Maintenance Schedule The intervals are calculated from continuous operation of the product.
  • Page 14: Troubleshooting

    Troubleshooting Note: If you cannot find a solution to your problem in this section, speak to Fantech technical support. Problem Cause Solution The fan impeller is not correctly Speak to Fantech technical support. balanced. Clean the fan impeller carefully. Refer There is dirt on the fan impeller.
  • Page 15: Disposal

    Problem Cause Solution Caution Set the installed switch to the OFF Defective motor winding. position. A fan replacement may be necessary. The fan speed does not get the nominal Speak to Fantech value. technical support. The speed control is not correctly set. Set the speed control correctly.
  • Page 16: Technical Data

    Technical data 10.1 Technical Data Overview Max. temperature of transported air, °F IP class Refer to the data sheet on the online catalogue at Fantech.net. Voltage, current, frequency Refer to the nameplate. Refer to section 1.6 Nameplate for more information. Motor data Refer to the motor nameplate or the technical documentation from the motor manufacturer.
  • Page 17: Wiring Diagrams For Ec Fans

    To Connect without a Motor Speed Controller To Connect to a Building Management System Motor Green Blue Black Brown Capacitor 120 Volt Supply Line — Black Green White Neutral — White Green — Ground Black Black or Brown 10.2.2 Wiring Diagrams for EC Fans Blue Green-yellow Note:...
  • Page 18 To Connect with an External Motor Speed Controller To Connect without an External Motor Speed Controller EC—10V, #498148 — Potentiometer Potentiometer Blue — Common 120 Volt Supply Yellow Green Red (+) 10VDC White 120 Volt Supply Black Green Black or Brown White Blue Black...
  • Page 19: Product Dimensions

    10.3 Product Dimensions Note: Dimensions are given in inches (mm). FG / K 4, #40402 & #40402A and FG / K 4XL 4 (102) 8 1/2 (216) 3 3/4 (95) 2 (51) 6 1/2 (165) 1 (25) 1 (25) EC, #56015 6 15/16 FG / K 4XL, #40403 &...
  • Page 20 last page Canada Latin America (800) 747 1762 (800) 565 3548 +52 55 1328 7328 support@fantech.net support@fantech.net support@fantech.net © Copyright Fantech All rights reserved Fantech reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.