Electric latch retraction

Advertisement

Quick Links

6100 & 6200 Series
Electric Latch Retraction
Installation Instructions
P Function and/or Monitors
1. Install the System Peripheral Components (782 Controller,
Controlling Switches, Power Transfer Hinge(s), etc.) and Raceways
(Table 1).
IMPORTANT:
Do not connect power until all components are installed.
Integral Power Supply: Connect the wires from the Power Transfer
Hinge, Controlling Switch(es) Console and Power (120 VAC) input
to the 782 Controller, as described in the controller installation
instructions.
Power Transfer Hinge: Follow the manufacturers' installation
instructions. The door leaf wires must exit through the door access
hole, underneath the device rear clamp.
2. Install Device (and optional Trim): Follow the installation
instructions for device (and trim). The Rear Clamp and End Cap are
NOT to be installed at this time.
3. Prepare Wiring Access Hole: Drill a 3/4˝ (19mm) diameter hole in
the door using the rear clamp center hole as a guide (Figure 1).
4. Install the rear clamp screws and fully tighten all device screws.
5. Check Device Action: Actuate the device by the touchbar (and trim).
Be sure that the door and device are operating properly and that the
door is opening freely and closing securely.
Wires from Power Supply to Device
(Minimum Gauge of Two-Conductor Cable)
Up to 40 Feet of Wire
Up to 60 Feet of Wire
Up to 100 Feet of Wire
Exit Device Rear clamp
Mounting Holes
(for reference only)
WARNING
This product can expose you to lead which is known to the state of California to cause cancer and birth defects or other
reproductive harm. For more information go to www.P65warnings.ca.gov.
WARNING
Attention Installer: Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening,
and ASSA ABLOY makes no representations or warranties concerning what such impact may be in any specific situation. When
retrofitting any portion of an existing fire-rated opening, or specifying and installing a new fire-rated opening, please consult with a
code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings.
1-855-557-5078 • www.assaabloy.com
Copyright © 2015, 2024, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Table 1:
16 Gauge
14 Gauge
12 Gauge
Figure 1: Door Preparation
6. Connect Device ELR Wires: The red (+) and black (–) polarized wires
from the inactive (hinge) end of the device connect to DEV 1 on the
782 (see the wiring diagram).
7. Connect Monitors (if used): Follow the connections shown in Figure
2. Wire nuts are not supplied.
8. Coordinated Door Operation: When two (2) devices are hooked to
the same 782, repeat steps 2. through 7. and connect the second
device to DEV 2.
9. Test System: With the power disconnected, verify there are no short
circuits throughout.
Apply power to console (if used) and to integral power supply.
Test the device; bolt should retract when the controlling switch closes
contacts and extend when the switch contacts open.
During momentary or continued operation the device status will
correspond to the switch contact status.
Note: The 782 Controller has an adjustable delay which causes the
electric latch to remain retracted while the controlling switch is open.
The Troubleshooting Guide (Table 2) provides modifications.
Inside Face of Door
Clear Channel Access
Required for Wire Connection
3/4˝ (19mm) Dia.
Wiring Access)
Exit Device
C
L
Conducting Hinge
or Approved Power
Transfer (by others)
Horizontal Reference
Device Centerline
4˝ Max.
Hinge Edge
of Door
C
L
80-9460-6016-000 01/24

Advertisement

loading
Need help?

Need help?

Do you have a question about the 6100 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Assa Abloy 6100 Series

  • Page 1 Attention Installer: Any retrofit or other field modification to a fire rated opening can potentially impact the fire rating of the opening, and ASSA ABLOY makes no representations or warranties concerning what such impact may be in any specific situation. When retrofitting any portion of an existing fire-rated opening, or specifying and installing a new fire-rated opening, please consult with a code specialist or local code official (Authority Having Jurisdiction) to ensure compliance with all applicable codes and ratings.
  • Page 2 1-855-557-5078 • www.assaabloy.com Copyright © 2015, 2024, ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.

This manual is also suitable for:

6200 series