Unit Control Board; Ignition Control Flash Codes - York DL-06 Installation Manual

Single package air conditioners and single package gas/electric units 6-1/2 to 12-1/2 ton
Table of Contents

Advertisement

TABLE 81: IGNITION CONTROL FLASH CODES
FLASHES
FAULT CONDITIONS
STEADY ON
Control Failure
HEARTBEAT
Normal Operation
1
Not Applicable
Pressure Switch
2
Stuck Closed
Pressure Switch Failed
3
To Close
4
Limit Switch Open
Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
5
Second Stage Gas Valve
Energized With First
Stage
Gas Valve Off
6
Ignition Lockout
No Power Or Control
STEADY OFF
Failure
Check
Alarm
History
Reset All
ASCDs for
One Cycle
Non Alarm
Condition Green
LED Flashing
Current Alarm
Flashed
Red LED
FIGURE 30: UNIT CONTROL BOARD
74
CHECK
Control
Pressure Switch
Venter Pressure Switch
Vent Blocked
Main Limit
AUX Limit
Gas Valve
Gas Flow
Gas Pressure
Gas Valve
Flame Sensor
24VAC or Control
167791-BIM-B-0606
Unitary Products Group

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dl-07Dl-08Dl-10Dl-12Du-06Du-07 ... Show all