Page 1
® TECHNICAL GUIDE Description R-410A ® These York Affinity™ packaged cooling/heating air conditioners are designed for outdoor installation. Only utility AFFINITY™ SERIES and duct connections are required at the point of installation. The single or two stage gas-fired heaters have aluminized steel DNX, DNY, DNZ MODELS tubular heat exchangers and spark to pilot ignition.
333491-YTG-B-0807 Nomenclature Cooling/Gas Unit Product Category Voltage Code D = Single Package Air Conditioner 06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60 Product Generation 1 = 1st Generation Nominal Gas Heating Output Capacity 2 = 2nd Generation (Nominal Low Gas Heat Output Capacity) 3 = 3rd Generation Factory Installed Gas Heat 036 = 36,000 BTUH...
Page 4
333491-YTG-B-0807 piece design adds greater water integrity. Rounded • Heat Exchangers - Are corrosion-resistant, aluminized- corners with water drip edges add to the attractive steel tubular construction to provide long-life, trouble-free appearance. The cabinet panels have a non-fibrous operation. The unique blow-through design also assures insulation that will not release insulation fibers into that condensate does not collect in humid areas when in conditioned area.
Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s • Dual Enthalpy Sensor - Additional sensor to single Affinity™ package units give you the flexibility and choices you enthalpy sensor.
Page 6
333491-YTG-B-0807 rails shall be removable, when required, to lower unit height. Coils: Filters shall be furnished and be accessible through a a. Evaporator and condenser coils shall have aluminum removable access door, sealed airtight. Units vertical discharge plate fins mechanically bonded to seamless internally and return duct configuration shall be designed to fit between enhanced copper tubes with all joints brazed.
333491-YTG-B-0807 Physical Data DNZ024-060 Single Stage Gas Heat Models Component DNZ024 DNZ030 DNZ036 DNZ042 DNZ048 DNZ060 Nominal Tonnage ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 26.1 30.4 37.3 42.6 50.3 58.2 ARI net capacity (Btu) 22.8 29.8 35.6 41.5 47.5...
Page 8
333491-YTG-B-0807 DNZ024-060 Two Stage Gas Heat Models Component DNZ024 DNZ030 DNZ036 DNZ042 DNZ048 DNZ060 Nominal Tonnage ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 26.1 30.4 37.3 42.6 50.3 58.2 ARI net capacity (Btu) 22.8 29.8 35.6 41.5 47.5 56.0 11.2...
Page 9
333491-YTG-B-0807 DNZ, DNY and DNX Unit Limitations Unit Limitations Size Model Unit Voltage Applied Voltage Outdoor DB Temp (Tons) Max (°F) 208/230-1-60 (2.0) 208/230-1-60 208/230-1-60 208/230-3-60 (2.5) 460-3-60 208/230-1-60 208/230-3-60 460-3-60 (3.0) 208/230-1-60 208/230-3-60 460-3-60 208/230-1-60 208/230-3-60 (3.5) 460-3-60 208/230-1-60 208/230-3-60 460-3-60 (4.0)
333491-YTG-B-0807 Indoor Blower Specifications Motor Size Model (Tons) Eff. Frame Variable (2.0) Variable (2.5) Variable (3.0) Variable Variable (3.5) Variable (4.0) Variable (5.0) Electric Heat Multipliers Voltage kW Capacity Multipliers Nominal Applied 0.75 0.92 0.92 0.92 1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.
333491-YTG-B-0807 Electrical Data DNZ024-060 Gas Heat OD Fan Supply Compressors Motors Blower Fuse Size (each) Volt (each) Motor Breaker (Tons) (Amps) Size RLA LRA MCC (Amps) 208/230-1-60 12.8 21.3 (2.0) 208/230-1-60 14.7 25.6 208/230-3-60 10.4 20.2 (2.5) 460-3-60 208/230-1-60 15.4 26.5 208/230-3-60 11.5 21.6...
Page 28
333491-YTG-B-0807 Typical DNX/DNY/DNZ024-060 Wiring Diagrams Typical DNZ024-060 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram Unitary Products Group...
Page 29
333491-YTG-B-0807 Typical DNZ024-060 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Unitary Products Group...
Page 30
333491-YTG-B-0807 Typical DNZ030-060 Cooling Unit with Single Stage Gas Heat 208/230-3-60 volt Wiring Diagram Unitary Products Group...
Page 31
333491-YTG-B-0807 Typical DNZ030-060 Cooling Unit with Two Stage Gas Heat 208/230-3-60 volt Wiring Diagram Unitary Products Group...
Page 32
333491-YTG-B-0807 Typical DNZ030-060 Cooling Unit with Single Stage Gas Heat 460-3-60 volt Wiring Diagram Unitary Products Group...
Page 33
333491-YTG-B-0807 Typical DNZ030-060 Cooling Unit with Two Stage Gas Heat 460-3-60 volt Wiring Diagram Unitary Products Group...
333491-YTG-B-0807 Weights and Dimensions DNX, DNY and DNZ Unit Weights Unit 4 Point Load Weight Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.) Size Model (Tons) Shipping Operating 24.5 (2.0) 24.5 24.75 (2.5) 24.25 (3.0) 24.8 (3.5) 24.8 (4.0) (5.0) Unitary Products Group...
Page 35
333491-YTG-B-0807 Gas Unit Dimensions Gas Unit Dimensions Dimensions Unit Size “A” “B” 024, 030, 036 33-1/2 18-1/4 , 042, 048, 060 41-1/2 23-1/8 1. DNY, DNZ Models. 2. DNX Models. Gas Unit Clearances Distance Distance Direction Direction (in.) (in.) Right Front Left Rear...
Page 36
333491-YTG-B-0807 Unit Dimensions Front and Bottom Unit Dimensions Back and Bottom Unitary Products Group...
Page 37
333491-YTG-B-0807 Unit Typical Duct Applications Unit Typical Slab on Ground Installation (Gas Model Shown) TO POWER SUPPLY FIELD SUPPLIED CONTROL WIRING TO DISCONNECT SWITCH INDOOR THERMOSTAT LOCATED TO REAR OF UNIT RETURN AIR DUCT SUPPLY AIR DUCT TO GAS SUPPLY LINE MANUAL GAS SHUT-OFF VALVE Unitary Products Group...
Page 38
333491-YTG-B-0807 Unit Typical Roof Curb Installation (Gas Model Shown) Unit Accessory Dimensions Roof Curb 1. 8” Roof Curb also available. Unitary Products Group...