Specifications
Honeywell VFD HAC10
The HAC10 is based on the market oriented for miniaturization, high reliability
and cost-competitive with performance.
Stable Vector control
Starting torque of 150%/0.5Hz is produced and provides robust power in the low-speed
region.
The motor auto-tuning function is optimized to maximize motor performance.
Ease-of-use
Convenient installation, small compact size, suppressed temperature increasing, high
protection.
Space efficient design and user benefits
Drive is installed Side-by-side on the panel, Various field networks, built-in EMC filter,
Extension IO option, replacements.
Hardware Specifications and Features
Items
Input
Output
Main control
performance
Basic product
function
MasterVert Specifications, HAC_V00

Specification

Single-phase 220V 50/60Hz
Voltage, Frequency
Three-phase 220V 50/60Hz
Three-phase 380V 50/60Hz
Voltage imbalance rate: <3%; Frequency: ±5%
Allow fluctuations
The distortion rate meets the requirements of IEC61800-2
Impact current when
Less than rated current
power on
Power factor
≥0.94 (with DC reactor)
Inverter efficiency
≥96%
Output under rated conditions: 3 phases, 0 to input voltage, error
Output voltage
less than 5%
Output frequency
0-600.00Hz
range
Output frequency
±0.5% of the maximum frequency value
accuracy
T3 model: 150% rated current for 89 seconds, 180% rated current
for 10 seconds, 200% rated current for 3 second
Overload capability
S2 model: 150% rated current 24 seconds, 180% rated current 3.4
seconds
Motor type
PMSM, AM
Motor control mode
No PG V/F control, no PG vector control
Modulation
Optimized space vector PWM modulation
Carrier frequency
1.0~16.0kHz
Speed control range
No PG vector control, rated load 1:100
Steady state speed
No PG vector control: ≤ 2% rated synchronous speed
accuracy
Starting torque
No PG vector control: 150% rated torque at 0.5Hz
Torque response
No PG vector control: <20ms
Digital setting: maximum frequency × ± 0.01%; analog setting:
Frequency accuracy
maximum frequency × ± 0.2%
Digital setting: 0.01Hz; Analog setting: Maximum frequency ×
Frequency resolution
0.05%
Starting frequency: 0.00~50.00Hz
DC braking capability
Braking time: 0.0~60.0s
Braking current: 0.0~150.0% rated current
Automatic torque increases 0.0%~100.0%
Torque boost
Manual torque increases 0.0% ~ 30.0%