Pump Installation; Pump Operations - Pentair HYDROMATIC S4MX Installation And Service Manual

Submersible pump with hazardous location motor end
Hide thumbs Also See for HYDROMATIC S4MX:
Table of Contents

Advertisement

Single phase pumps with capacitor
start have a run and a start winding
each drawing a different current.
To adequately protect these
windings with the appropriate
heaters, consult the factory.
NOTE: red lead is always
start winding of pump using
single phase.
Pump
Installation
installing Sump Level Control
Float Controls:
In either simplex, duplex or
triplex systems the lower or
turn-off control is to be set to
maintain a minimum level in the
sump. This level shall be no more
1
than 3
" from the top of the
4
motor housing down to the
surface of the sewage.
The second or turn-on control is
set above the lower turn-off
control.
The
exact
between the two floats must be a
compromise between a frequent
pumping cycle (10 starts per hour
max.) to control septicity, solids
and a slower cycle for energy
economy. This distance should
be determined by the engineer or
consulting engineer depending on
the conditions of the application.
For installation of Hydromatic
supplied level controls refer to
your system's installation and
service manual.
installing Pump in Sump:
Before installing pump in sump
lay it on side and rotate impeller.
Impeller may be slightly stuck
due to factory test water so it must
be broken loose with small bar or
screwdriver in edge of vanes. The
impeller should turn freely. Do
not connect the power until after
this test.
Clean all trash and sticks from
sump and connect pump to piping.
A check valve must be installed
on each pump. A gate or plug
valve in each pump discharge
is highly recommended. This
valve should be installed on the
discharge side of the check valve
so if necessary to service the
check valve the line pressure can
be cut off. Single pump systems
are sometimes installed without a
check valve where it is desirable
to self-drain the discharge line to
prevent freezing. This can be done
only with short discharge lines;
otherwise water will return to the
sump and cause short cycling of
the pump.
Making Electrical Connections:
All electrical wiring must be in
accordance with local code, and
only qualified electricians should
make the installations. Complete
wiring diagrams are included for
distance
use in making the installation. All
wires should be checked for shorts
to ground with an ohmmeter or
Megger after the connections
are made. This is important, as
one grounded wire can cause
considerable trouble.
iMPOrTANT: if equipment
is not properly wired and
protected as recommended,
Hydromatic warranty is void.
See Page 4.
Heat Sensor and Seal
Failure Connections:
If a Hydromatic control panel is
used, terminal blocks are provided
for heat sensor, seal failure
connections (See Panel Schematic).
If a control panel is supplied by
others, it must allow heat sensor
and seal failure terminations.
Pump
Operations
Starting System:
1. Double
check
connections.
2. Turn pumps to Off position on
H-O-A switches.
3. Turn on breakers.
4A.When using single phase
pumps, make sure red pump
lead is connected to capacitor
circuit, connect amprobe to
pump power cord and turn
pump on. Pump will show high
amp draw momentarily, then
as pump comes off start
wiring, amps will drop to
normal nameplate amps.
4B.When using three phase
pumps (230/460/575), turn
H-O-A
switch
position on one pump and
notice operation. If pump is
noisy and vibrates, rotation is
wrong. To change rotation,
interchange any two line leads
to pump. Do not interchange
main incoming lines. Check
rotation of all pumps in this
same manner.
5. Now set both H-O-A switches
to Auto position and allow
water to rise in sump until one
pump starts. Allow pump to
operate until the level drops
to turn-off point.
6. Allow sump level to rise to
start other pump(s). Notice run
lights to panel. Pumps should
alternate on each successive
cycle of operation.
7. Turn both H-O-A switches to
Off position and allow sump to
fill to the override control level(s).
8. Turn switches to Auto position,
and pumps should start and
operate together until level
drops to turn-off point.
all
wire
to
Hand
3 3

Advertisement

Table of Contents
loading

Table of Contents