Installation Example - Gree EVO S Series Owner's Manual

Mini chiller
Table of Contents

Advertisement

eries
Model Line-Up
Model Name
HLR8Pd/Na-K
HLR10Pd/Na-K
HLR12Pd/Na-M
HLR14Pd/Na-M
Notes:
1
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 40°C/45°C,Outdoor Air Temperature 7°C DB/6°C WB;
2
Capacities and power inputs are based on the following conditions:
Indoor Water Temperature 12°C/7°C,Outdoor Air Temperature 35°C DB/-.

6 Installation Example

CASE 1: Connection of Terminals for Heating and Cooling (Under floor Loop, Fan Coil Unit, and
Radiator)
T
Notes:
(a) The two-way valve is very important to prevent dew condensation on the floor and radiator while cooling mode;
(b) Type of thermostat and specification should be complied with installation of this manual;
(c) The by-pass valve must be installed to secure enough water flow rate, and should be installed at the collector.
CASE 2: Connection between the Electric Heater and the Main Unit
Two groups of electric heaters are available, as well as control terminals for two groups of auxiliary electric
heaters. These two groups of electric heaters can be activated at the same time. When only one group of the
electric heater is installed, please follow the wiring of any group of the diagram shown below.
(1) See the following statement for installation of two groups of auxiliary electric heaters, including wiring of the
AC contactor, the thermostat and the tank-type electric heater.
Wiring of the AC Contactor
L1, L2 and L3 are three-phase input terminals. T1, T2 and T3 are three-phase output terminals. A1 and A2 are
terminals of input and output signals which are used to control the AC contactors. NO and NC are normally open
and closed terminals of the AC contactors.
1
Heating
,kW
8
10
12
14
Remote room thermostat (field supplied)
B
Bypass valve (field supplied)
High temperature line
Capacity
2
Cooling
,kW
6.2
7.5
9.5
11
Under Floor Coil
T
M
FCU 1
FCU 2
M
2-Way Vavle (field supplied)
Controll Cable
Low temperature line
10
Mini Chiller
Power supply
220-240V,1Ph,50Hz
380-415V,3Ph,50Hz
B
Radiator

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hlr8pd/na-kHlr12pd/na-mHlr10pd/na-kHlr14pd/na-m