Fieldbus Monitoring Values; V1.2.17 Dc- Link Actcur R % # ,# 1158; V1.2.18 Cr Est Factor # ,# # # 1101; V1.3.1 Fb Contr Ol Wor D # 1160 - Vacon NXP ARFIFF03 Applications Manual

Grid converter
Table of Contents

Advertisement

arfiff03 Grid Converter
V1.2.17
DC- Link ActCur r
Calculated DC- Link Cur r ent in %, 100 % = P2.1.3 Gr id Conver ter Rated Cur r ent.
V1.2.18
Cr est Factor
Cr est factor of the cur r ent.
4.2.3

Fieldbus monitoring values

V1.3.1
FB Contr ol Wor d
The contr ol wor d fr om fieldbus. The table below is for
(P2.10.19) in bypass oper ation for such fieldbus boar d that natively suppor ts this or can
be par am eter ised to bypass mode. See other profile selections fr om chapter Status and
Contr ol Wor d.
DC Char ge
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
Local contacts: http://drives.danfoss.com/danfoss- drives/local- contacts/
%
# ,# # # ID1101
ID 1160
Signal
0 = Open MCB.
1 = Close DC char ge contactor , MCB closed automatically.
0 = Stop Command
Star t
1 = Star t Command
Reset
0>1 Reset fault.
Fieldbus
0 = No contr ol fr om fieldbus
Contr ol
1 = Contr ol fr om fieldbus
Watchdog
communication between the fieldbus master and the drive.
Can be used to contr ol RO or the parameter dir ectly by ID
FB DIN2
number . G2.4.1
Can be used to contr ol RO or the parameter dir ectly by ID
FB DIN3
number . G2.4.1
Can be used to contr ol RO or the parameter dir ectly by ID
FB DIN4
number . G2.4.1
# ,#
ID1158
FB Contr ol Wor d ID1160
Comment
squar e wave clock. This is used to check data
VACON® · 43