*1: There is no internal protection circuit in the output relay of the PLC; therefore when activating an inductive load,
we suggest you parallely connect a reverse current protection diode to extend the life of the contact.
- The diode has to be able to endure max. 5 ~ 10 times of load voltage.
- The positive current of the diode has to be bigger than load current.
*2: Manual exclusive output uses external circuit and forms an interlock, together with the PLC internal program, to ensure
safety protection in case of any unexpected errors.
*3: There is no internal protection circuit in the output relay of the PLC; therefore when activating an inductive load, we
suggest you parallely connect a surge absorber (0.1uF + "100ohm to 120ohm") to reduce the noise on AC load and
extend the life of the contact.
Transistor Output Wiring Circuit (Sink):
C0
Y0
5
7
3
2
3
UP
Y0
7
8
5
2
3
3
*1: Manual exclusive output uses external circuit and forms an interlock, together with the PLC internal program, to
ensure safety protection in case of any unexpected errors.
*2: Use a zener diode (39V) in the PLC to protect the transistor output. When activating inductive load, we sugget you
parallely connect a reverse current protection diode.
Transistor Output Wiring Loop (Source):
ZP
Y7
1
3
2
3
5
*1: Manual exclusive output uses external circuit and forms an interlock, together with the PLC internal program, to
ensure safety protection in case of any unexpected errors.
*2: Use a zener diode (39V) in the PLC to protect the transistor output. When activating inductive load, we sugget you
parallely connect a reverse current protection diode.
C1
Y1
C2
Y2
Y3
MC2
MC1
6
8
MC1
MC2
4
Y1
Y2
Y3
Y4
Y5
Y6
Y7
10
10
MC2
MC1
6
MC1
MC2
4
9
Y3
Y1
Y0
Y6
Y5
Y4
Y2
MC2
MC1
6
MC1
MC2
7
8
4
9
DO NOT wire empty terminal
Y4
Y5
Emergency stop
1
Fuse
6
Manual exclusive output*1
9
[ Figure 10 ]
DC power supply
Incandescent light (resistive load)
ZP
Reverse current protection diode*2
Inductive load
6
Resistive load
[ Figure 11 ]
Y1, Y3 (refer to other wiring methods)
Y6, Y7 (refer to other wiring methods)
Emergency stop
UP
Fuse
Manual exclusive output*1
DC power supply
6
Incandescent light (resistive load)
Reverse current protection diode*2
[ Figure 12 ]
Inductive load
Resistive load