• Remove the transparent label remaining in the upper part of the adhesive sheet
and stick it over the previous one affixed to the loading point.
Avoid the emission of the fluorinated gas contained here.
• Make sure that the fluorinated gas is never released into the atmosphere
during installation, assistance and disposal.
• Whenever a fluorinated gas leak is detected, the leak must be found and
repaired as quickly as possible.
ONLY qualified personnel must provide assistance on this product.
Any use of fluorinated gas in this appliance, e.g. during manual movement of the
product or re-loading the gas, must be compliant with the regulations regarding
determined fluorinated greenhouse gases and any applicable local laws.

2.6.7 - Connection of the condensate drain line

Connect a drain pipe, of appropriate length, to the indoor unit condensate drain pipe, and block it with a strap.
Make it run inside the duct parallel to the system pipes, fastening it to the same using straps.
Do not tighten the straps excessively in order to prevent damage to the insulation of
the pipes and narrow the drain pipe.
Where possible, make the condensate liquid flow directly into a rainwater gutter.
If the drain pipe is fed into a sewage system, it is necessary to bend the pipe in order
to create a siphon (figure 25), in order to avoid the diffusion of unpleasant odours into
the environment.
The siphon bend must never be at a level below 1500 mm from the lower wire of the
appliance (figure 25).
If draining is into a recipient (figure 26), this must never be closed so as not to prevent
counter-pressures such to compromise the operation, and the pipe itself must never
reach the level of the liquid deposited.
Check the correct run-off of the condensate liquid through the relative pipe by very
slowly pouring approx. 1/2 litre of water into the collection tray of the indoor unit (figure
27).

2.7 - ELECTRIC CONNECTIONS

2.7.1 - Electric connection between indoor and outdoor units

The connection wiring diagrams are illustrated in figure 48.
The electric connection between the indoor units must have the features stated in the table of the following
page.
The connection cable between the outdoor unit and the indoor units must be the "H07RN-F" type.
2.7.2 - Indoor unit electric connection (Figure 29a)
a. Remove the panel (21)
b. Unscrew the screw and remove the protection (22).
c. Connect the cables to the terminal board (23) as illustrated in figure 48.
d. Wrap the cables not connected to the terminals in electrician's tape, in a way that they cannot
touch any electric component.