Operation - Ecosoft ROBUST MINI Installation And Operation Manuallines

Reverse osmosis systems
Table of Contents

Advertisement

Available languages

Available languages

INSTALLATION AND OPERATION GUIDELINES FOR REVERSE OSMOSIS SYSTEMS ECOSOFT ROBUST MINI,
ROBUST 1500, ROBUST PRO, ROBUST 3000, ROBUST 3000MAX, ROBUST 4000
Regulate

6. OPERATION

RObust reverse osmosis system should be used for purification of cold water only.
Monitoring of the system is carried out based on the readings of pressure gauges* and evaluation
of production.
Pressure after pre–filters (left pressure gauge). If pressure after pre–filters is less than 1 bar, this
may indicate low mains pressure or clogged pre–filters. Test pressure at the feed adapter site. If it
exceeds reading on the pressure gauge significantly, replace pre–filters. Otherwise, low feed water
pressure is at fault and has to be sorted out. If the 1st pressure gauge displays over 5 bar after the
system switches on, power down the system immediately, disconnect water supply, and install a
pressure regulator upstream of the system. Then, continue setting up the system. Recommended
feed water pressure is 3,5 bar.
Operating pressure (right pressure gauge). If operating pressure in the membrane is lower than
4 bar or falls to the value of the feed water pressure, this can be caused by the following:
• motor power supply fault (possibly due to broken/torn pump motor cord);
• air trapped inside pump's chamber;
• jamming of the pump with solids such as carbon fines (if carbon filter was not properly rinse
before use).
Generally, if operating pressure reading on the 2nd pressure gauge falls below its normal range,
contact your dealer's service. If pressure on 2nd pressure gauge is over 7 bar, this could be due
to pressure regulator failure or the RO system's high pressure switch fault. Contact your dealer's
service for help.
Performance. Reduced system flow rate is a sign of
exhausted capacity of pre-filters. Untimely replacement
of them leads to contamination of membranes and
complete loss of their productivity.
With a significant drop in system performance,
replacement of reverse osmosis membranes is required.
In the event of long breaks in the system operation
(more than 2 weeks), disinfect the system as described in
paragraph 7 and shut off the water supply to the system.
* There are no pressure gauges in the Robust Mini product, they need to be
installed additionally to check the pressure in the system.
This value only applies to the RObust 3000MAX and RObust 4000 models.
1
This manual is the intellectual property of Ecosoft. Copying and reprinting is prohibited. © 2024
NOT regulate
Pressure
after cartridges
lower than 1 bar
lower than 4 bar
Change
cartridges
higher than 5 bar
higher than 7(8)
Install a pressure
regulator
Figure 7.
Operating parameters of the system
23
Operating
pressure
Contact after
sale service
bar
1
Contact after
sale service