Taco LoadMatch L0410-Y6CI1-FHAN Instruction Sheet

Cartridge circulators

Advertisement

Quick Links

SUPERSEDES: May 1, 2010
Plant I.D. 001-1178
APPLICATION:
1. Maximum operating pressure is 200 psi (1379 kPa).
2. Maximum water temperature not to exceed nameplate rating.
3. Cast iron circulators are to be used for closed loop systems. Bronze or stainless steel circulators are to be used for
open loop, fresh water, or potable water systems.
4. Taco Cartridge circulator pumps are for indoor use only – employer uniquement a l´interieur.
INSTALLATION:
WARNING: To avoid electrical shock, disconnect the power supply to the circulator and the main
electrical unit.
1. Mounting position – Circulator must be mounted with the motor in a horizontal position. They may be mounted
vertically with the motor up, provided that the system pressure is at least 20 psi (138 kPa).
2. Rotating body – Body has an arrow on the front that indicates direction of flow. To rotate body, remove the four body
bolts, rotate body and replace bolts. Make sure that the junction box is NOT located underneath the circulator. (The
junction box must NOT be located in the 6 o'clock position, as viewed from the motor end.)
3. Electrical connections – Observe all applicable codes when connecting to power supply. The motor is impedance
protected, and does not require overload protection. Either colored wire from the capacitor box can be attached to
either colored wire from the power supply. There is no "hot" or "common" wire leading from the capacitor box. Typical
installation would be to attach the white wire to the white (common) power supply wire and either the yellow or blue
wire to the black (hot) power supply wire. The pump cannot run backwards.
WARNING: Do not use in swimming pool or spa areas; pump has not been investigated for this
application.
WARNING: In the event the retaining screws have been pulled out of the housing, DO NOT replace
them. Use of any other screw may short out the stator windings, creating a risk of elec-
trical shock.
CAUTION: When installing electrical connections, do not apply mechanical loads to the capacitor
box; otherwise, retaining screws may be pulled out of the housing, making circulator
unusable.
CAUTION: Installations at higher elevations over 5000 feet must have higher fill pressure of 20 psi
minimum to prevent pump cavitation and flashing. Premature failure may result. Adjust
expansion tank pressure to equal fill pressure. A larger size expansion tank may be required.
4. Fill system with tap water – The system must be filled before operating the circulator. The bearings are water lubri-
cated and should not be allowed to operate dry. Filling the system will result in immediate lubrication of the bearings.
It is always good practice to flush a new system of foreign matter before starting the circulator.
5. Circulator operation – Operate the circulator for 5 minutes immediately after filling system to purge remaining air from
the bearing chamber. This is especially important when installing the circulator during the off-season.
CAUTION: 1. The addition of petroleum based fluids or certain
chemical additives to systems utilizing TACO
equipment voids the warranty.
2. Use supply wires suitable for 90°C – ATTENTION:
Employer des fils d´alimentation adequats pour 90°C.
Instruction Sheet
®
LoadMatch
Cartridge Circulators
102-115
EFFECTIVE: October 1, 2010
A Taco resource – saving product

Advertisement

loading

Summary of Contents for Taco LoadMatch L0410-Y6CI1-FHAN

  • Page 1 3. Cast iron circulators are to be used for closed loop systems. Bronze or stainless steel circulators are to be used for open loop, fresh water, or potable water systems. 4. Taco Cartridge circulator pumps are for indoor use only – employer uniquement a l´interieur. INSTALLATION: WARNING: To avoid electrical shock, disconnect the power supply to the circulator and the main electrical unit.
  • Page 2 TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2010 TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...