Taco GT Horizontal 302-054 Operation And Maintenance Manual

Horizontal split casing pumps

Advertisement

Quick Links

SUPERSEDES: New
Plant ID No. 001-3930
SAFETY REQUIREMENTS
These operating instructions must be complied with during instal-
lation, operation and maintenance, and must be read by the
operator before commencement of any work. Only fully qualified
personnel may carry out work on the pump set. Non-compliance
with these instructions may lead to damage to the equipment,
serious injury or hazard to the environment.
CAUTION: Read these instructions before
putting the pump into service.
CAUTION: Installation and operation should
be carried out by qualified personnel only.
CAUTION: Danger of electrocution. Electric
supply must be isolated before working on
the pump set.
CAUTION: Electrical work should only be
carried out by qualified personnel.
A:
GENERAL
Taco GT pumps are single stage double suction axially split
pumps supplied either bare shaft or complete with an electric
motor. Details of the pump type and model, serial number and
operating data are indicated on the pump nameplate.
The pump must be installed and operated in full compliance with
these instructions. The pump may not be operated outside the lim-
its specified on the nameplate and within this manual. The pump
should only be operated by skilled trained personnel. The manu-
facturer will not accept liability if these instructions are not fol-
lowed. This manual does not take into account any specific local
regulations or bylaws that may be applicable, and it is the respon-
sibility of the installer to ensure compliance with such regulations.
A1: Application
Taco GT pumps are suitable for continuous pumping of clean
water and liquids with properties similar to water, with fine solids
content not exceeding 200 ppm.
A2: Area of Operation
May be installed within a building or externally. Wherever
installed, protect the pump from frost, snow and flooding. Care
must be taken to ensure that cold weather will not cause the
pump or pipes to freeze, and installers may wish to consider lag-
ging or trace heating.
Split Casing Pumps
Operations and Maintenance Manual
GT Horizontal
A3: Spare Parts
Spare parts are available from Taco distributors which can be
located at www.taco-hvac.com. Please quote the pump model
and serial number for all spares enquiries.
The pump user is strongly recommended to carry replacement
spares for parts which are wearing items:
• Mechanical seal or gland packing
• Casing wear ring
• Shaft sleeve
• Casing gasket
• Gland plate gasket
Only genuine Taco spare parts should be fitted. Use of other
parts will invalidate the manufacturer's warranty and liability for
consequential damage.
A4: Transport
The pumpset must remain horizontal during transport and lifting.
Only use certified lifting equipment suitably rated for the weights
to be lifted.
When hoisting the bareshaft pump only, secure a sling of suitable
load capacity around the suction flange and bearing housing as
indicated (see Figure 1). For new installations, keep the pump on
its original pallet while moving around site or on transport. If the
original pallet is not available, the pump should be securely bolted
to a pallet of generous size to ensure stability.
Figure 1: Attaching a Sling to the Pumpset
Lifting the complete pumpset (pump, motor and bedplate) may
be carried out using a forklift or with a set of lifting chains secured
to the lifting points provided on the bedplate (see Figure 2).
302-054
EFFECTIVE: March 1, 2009

Advertisement

loading
Need help?

Need help?

Do you have a question about the GT Horizontal 302-054 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Taco GT Horizontal 302-054

  • Page 1 • Shaft sleeve putting the pump into service. • Casing gasket • Gland plate gasket Only genuine Taco spare parts should be fitted. Use of other parts will invalidate the manufacturer’s warranty and liability for CAUTION: Installation and operation should consequential damage.
  • Page 2 A7: Baseplate Setting CAUTION: When using a forklift, particular care should be taken to properly balance the Use blocks and shims under base for support at foundation bolts load. The electric motor may be significantly and midway between bolts to position base approximately 1 inch above the concrete foundation with the studs extending through heavier or lighter than the pump.
  • Page 3 Any changes to smooth- ness of operation should be investigated immediately. The pump Taco GT pumps should not be continually operated at a flowrate should be visually checked periodically. below 30% of the peak efficiency flowrate unless otherwise specifically agreed by the manufacturer.
  • Page 4 B5: Thermal Shock C2: Lubrication Taco GT pumps are not designed to withstand rapid changes in The pump bearings are provided with grease fittings. Apply a high temperature. Where a pump is handling hot liquids, the liquid quality bearing grease (Shell Alvania or equal) every 2000 hours, should be introduced slowly allowing the pump to gradually or every six months, whichever comes first.
  • Page 5 Impeller passages should be free from debris. Check for cavita- CASING SPLIT tion damage to the eye of the impeller, where the liquid enters. FLANGE NUTS Cavitation is caused when there is insufficient suction pressure to the pump. Pitting or spongified surfaces to the impeller vanes GLANDPLATE may be seen.
  • Page 6 TYPICAL CROSS SECTION MECHANICAL SEAL PUMP 26 27 34 49 35 20 21 22 23 SECTION A–A FRONT VIEW – PUMP ONLY...
  • Page 7 REF. DESCRIPTION DESCRIPTION DESCRIPTION Wear Ring Seal Retainer Cap Bolt Bearing Retaining Nut (DE) Impeller Bearing Housing (NDE) Bearing Housing (DE) Casing Drain Plug Bearing Housing Plug Impeller Key Casing Stud Bearing Retaining Nut (NDE) Shaft Casing Nut Bearing Retaining Washer (NDE) Outer Shaft Sleeve Pipe Plug Bearing (NDE)
  • Page 8: Limited Warranty Statement

    TACO, INC., 1160 Cranston Street, Cranston, RI 02920 Telephone: (401) 942-8000 FAX: (401) 942-2360. Copyright 2009 TACO (Canada), Ltd., 8450 Lawson Road, Unit #3, Milton, Ontario L9T 0J8. Telephone: 905/564-9422. FAX: 905/564-9436. TACO, Inc. Visit our web site at: http://www.taco-hvac.com...