Carrier AquaEdge 19XR3-E Start-Up, Operation And Maintenance Instructions Manual page 30

Table of Contents

Advertisement

The applicable configuration tables are dependent upon the starter/
VFD type and manufacturer. For all factory unit-mounted equip-
ment all starter configurations should be completed at the factory,
but will need to be verified during chiller commissioning.
For starters without ISM, the appropriate starter selection must be
configured through MAIN MENU →CONFIGURATION
MENU→ FACTORY →VFD/STARTER OPTION.
Options are as follows:
0 = Starter with ISM
1 = Free Standing VFD with ISM [North America options:
Toshiba VFD, Allen Bradley PF7000, PowerFlex 700L (unit
mount)]
3 = Rockwell LF2 VFD (LiquiFlo2)
4 = Eaton VFD (LCX9000)
5 = Rockwell STD VFD (Allen Bradley PowerFlex 755)
7 = Danfoss VFD
8 = Benshaw Starter (Wye-delta or Solid State starters with
MX3
1
and no ISM)
For constant speed machines verify all listed parameters in ISM
Configuration. Similarly, for unit-mounted VFDs verify all
(Main MenuConfiguration MenuCONF_OPTOption Configuration [for all Starter/VFD options])
PARAMETER
Auto Restart Option
Swift Restart Option
Common Sensor Option
EC/HG (HGBP) Valve Option
EC/HG (HGBP) Valve Selection
HPR VLV Option
Tower Fan High Setpoint
Refrig Leakage Option
Oil Cooler EXV Option
Customer Alert Option
Ice Build Option
Vapor Source SV Option
Vapor Source SV Delay
Evap Liquid Temp Opt
Evap App Cal Selection
(Main MenuConfiguration MenuOption2Option Configuration [for all Starter/VFD options])
PARAMETER
IOB3 Option
IOB4 Option
Free Cooling
Water Pressure Option
Water Flow Measurement
Water Flow Determination
Marine Option
Table 8 — Typical Job Site Parameters
CONF_OPT — Disable/Enable
CONF_OPT — Disable/Enable
CONF_OPT — Disable/Enable
CONF_OPT — 0=No HGBP valve, 1= Continuous (two contactor control - one to open, one to close with
feedback of fully closed and open position), 2= on/off (1 contactor control - either on or off and no
feedback), 3 = mA (control by 4-20 mA signal with feedback)
CONF_OPT - 0 = Disable, 1=Surge (HGBP valve activates when surge prevention is high), 2= Low Load
(EC valves activates based on IGV position and delta T for low load operation). EC valve is to Open when
IGV position is less than the configured ECV Open IGV1 Position and (cooling mode) the water Delta T
(ECW-LCW) is less than or equal to ECV On DT for Low Load minus ECV Low Load DB. EC valve is to
Close when IGV position is greater than the ECV Close IGV1 Position and (cooling mode) water Delta T is
greater than the ECV Off DT for Low Load plus ECV Low Load DB. 3=Combined (EC valves controlled by
both surge and low load algorithms)
Disable/Enable. When enabled, values for HPR VLV Delta Pos 0% (4 mA), HPR VLV Delta Pos 100% (20 mA),
HPR VLV Min Output (minimum output %), and HPR VLV Deadband can be set. 
Typically HPR VLV Deadband must be set at 0.5 psig for normal operation.
Default 75°F
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Disable/Enable
Default 5 min
Disable/Enable
0 = Saturation Temp, 1 = Refrigerant Temperature
Table 9 — Typical Job Site Parameters
No/Yes (always "Yes" for North America 19XRs)
No/Yes (select if optional fourth IOB board is present)
No/Yes
0=No, 1=WTR Flow PD TRD (dedicated water pressure transducers), 
2=WTR Flow PD TRM (differential water flow pressure transmitter - 4-20 mA)
0=No, 1=WTR Flow MTR (4-20 mA water flow sensors), 
2=WTR Flow PD (based on water pressure drop measurement)
0=Saturated Temp, 1=Flow Switch, 2=Water Flow PD
Disable/Enable
30
parameters listed in UM VFD Configuration Tables 8-11. Verify
against chiller electrical nameplates.
For units that are doing native communicating Modbus without a
UPC gateway ensure that the Modbus Gateway Option in MAIN
MENU→CONFIGURATION MENU→MODBUS PRIMARY
is changed to 0=Native along with baud rate and Secondary De-
vice Address. Baud rate is typically 9,600 and secondary address
is 1.
Liquid bypass option allows bypass of the economizer. When En-
abled and available the 19XR with frame C bypass valve will
modulate based on lift and % Amps to allow for high cooling ca-
pacity at low load.
Dynamic Demand Limit is a control feature which will demand
limit the chiller to prevent refrigerant stack-up due to high refrig-
erant flow at low lift. It is required to set LCW at Selection Point
and LCDW at Selection Point as well as Enable the Dynamic De-
mand Limit function to make this feature active.
1. Third-party trademarks and logos are the property of their respective
owners.
TABLE
TABLE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquaedge 19xrAquaedge 19xr6Aquaedge 19xr7

Table of Contents