Motor And Oil Cooling Cycle; Vfd Cooling Cycle - Carrier AquaEdge 19XR3-E Start-Up, Operation And Maintenance Instructions Manual

Table of Contents

Advertisement

MOTOR AND OIL COOLING CYCLE

The motor and the lubricating oil are cooled by liquid refrigerant
taken from the bottom of the condenser vessel (Fig. 8 and 9). Re-
frigerant flow is maintained by the pressure differential that ex-
ists due to compressor operation. After the refrigerant flows past
an isolation valve, an in-line filter, and a sight glass/moisture in-
dicator, the flow is split between the motor cooling and oil cool-
ing systems.
CAUTION
To avoid adverse effects on chiller operation, consideration
must be made to condenser water temperature control. For
steady state operation, the minimum operating refrigerant
pressure differential between cooler and condenser is approxi-
mately 20 psi (138 kPa) with a maximum evaporator refriger-
ant temperature of 65°F (18°C). Consult Chiller Builder for re-
quired steady state operational limits. Inverted start conditions
are acceptable for short durations of time, but for periods ex-
ceeding 5 minutes, a special control solution strategy should
be used to allow the chiller to establish a minimum refrigerant
pressure differential, and thereby adequate equipment cooling.
Flow to the motor cooling system passes through an orifice and
into the motor. Once past the orifice, the refrigerant is directed
over the motor by spray nozzles. The refrigerant collects in the
Fig. 7 — Refrigeration Cycle — 19XR(V) Two-Stage Compressor
bottom of the motor casing and is then drained back into the cool-
er through the motor refrigerant drain line. An orifice (in the motor
shell) maintains a higher pressure in the motor shell than in the
cooler. The motor is protected by a temperature sensor embedded
in the stator windings. An increase in motor winding temperature
past the motor override set point overrides the temperature capaci-
ty control to hold, and if the motor temperature rises 10F (5.5C)
above this set point, the controls close the inlet guide vanes. If the
temperature rises above safety limit, the compressor shuts down.
Refrigerant that flows to the oil cooling system is regulated by ex-
pansion valves. The expansion valves regulate flow into the oil/re-
frigerant plate and frame-type heat exchanger (the oil cooler in
Fig. 8), and control oil temperature to the bearings. The refrigerant
leaving the oil cooler heat exchanger returns to the chiller cooler.

VFD Cooling Cycle

If equipped with a refrigerant-cooled unit-mounted VFD, the re-
frigerant line that feeds the motor cooling and oil cooler also feeds
the heat exchanger on the unit-mounted VFD. Refrigerant is me-
tered through an orifice as refrigerant is leaving the VFD heat ex-
changer. The refrigerant leaving the heat exchanger returns to the
cooler. Alternatively, if equipped with an air-cooled unit-mounted
VFD the cooling of the VFD is integral to the VFD by means of
cooling with ambient air.
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aquaedge 19xrAquaedge 19xr6Aquaedge 19xr7

Table of Contents