Carrier AquaEdge 19XR3-E Start-Up, Operation And Maintenance Instructions Manual page 116

Table of Contents

Advertisement

NOTE: This can be accomplished through BMS interlock with Carrier controls (typically via BACnet or Modbus) or
hardwire connections to pumps. Chiller MUST maintain pump control for freeze protection purposes. If answer to
above is "No" the customer must sign off that this is not installed and a copy must be kept with the startup paperwork
since this can result in loss of warranty coverage.
INITIAL START:
Line up all valves in accordance with instruction manual:
Start water pumps and establish water flow
Oil level OK and oil temperature OK
Check oil pump rotation-pressure
Check compressor motor rotation (motor end sight glass) and record:
Clockwise
Restart compressor, bring up to speed. Shut down. Any abnormal coastdown noise?
Yes*
No
*If yes, determine cause.
START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:
A: Trim charge and record under Charge Refrigerant section.
B: Take at least two sets of operational log readings and record.
C: After machine has been successfully run and set up, shut down and mark shutdown oil and refrigerant levels.
D: Give operating instructions to owner's operating personnel.
Hours Given:
Hours
E: Call your Carrier factory representative to report chiller start-up.
At startup, chiller connectivity was completed:
the PIC6 ETH0 MAC ADDRESS: __________________________
the PIC6 ETH0 Ethernet address: _________________________
the PIC6 Gateway Address: ______________________________
Antenna Wired and Mounted
iOT Certificate Present
Ping Test Passed
Cloud Test Passed
Sent Command Center Registration Data (below)
Jobsite Name: _________________________
Job Street Address: ________________________
Jobsite City, State, Zip Code: ___________________________
CCS Office: _____________________
CCS Market: _____________________
Carrier Contract or Job Number: _____________________________
SIGNATURES:
CARRIER
TECHNICIAN
___________________________________________
DATE
CUSTOMER
REPRESENTATIVE ___________________________________________
DATE