19XR PIC6 CFGSURGE SURGE CORRECTION CONFIG TABLE CONFIGURATION SHEET
DESCRIPTION
Surge Line Configuration
0=PR, 1=Delta T
IGV1 Pos Configuration
0-Degree, 1=Percentage
Surge Delta Tsmax
Surge Delta Tsmin
PR at Full Load Opening
PR at Min. Opening
IGV1 Full Load Open Deg
Sound Ctrl IGV1 Open Deg
IGV1 Minimum Open Deg
IGV1 Actuator Max Deg
Surge Line Offset
Surge Line Lower Deadband
Surge Line Upper Deadband
Surge Line Shape Factor
Sound Line Shape Factor
Surge Line Speed Factor
Surge Delay Time
Surge Time Period
Surge Delta Amps %
Rampdown Factor
GV1 Close Step Surge
VFD Speed Step Surge
EC Valve Step Surge
Surge Profile Step
Surge Profile Offset
High Efficiency Mode
GV Jumpover Option
19XR PIC6 CTRL_ID CONTROL IDENTIFICATION TABLE CONFIGURATION SHEET
DESCRIPTION
CCN Element Number
CCN Bus Number
CCN Baud Rate
Device Description — 19XRPIC6
Location Description (User-defined 
24-digit character string)
Software Part Number: 
SCG-SR-2-20S200200
Serial Number =
19XR PIC6 LQBP - LOW LOAD CONTROL IDENTIFICATION TABLE CONFIGURATION SHEET
DESCRIPTION
ECO LBP VLV Option
ECO LBP VLV Limit
DSH Deadband for LBP
ECO LBP VLV EVap Appro
Dynamic Demand Limit
Ignore DDL Time
LCW at Selection Point
LCDW at Selection Point
100% Lift Demand Limit
Middle Lift Percent
Middle Lift Demand Limit
20% Lift Demand Limit
LCW at Selection Point
LCDW at Selection Point
RANGE
0 to 1
0 to 1
0.0 to 150.0
0.0 to 150.0
1.0000 to 5.0000
1.0000 to 5.0000
90 to 120.0
10.0 to 40.0
0.0 to 10.0
90.0 to120.0
1.0 to 3.0
0.5 to 3.0
0.1 to 3.0
–1.000 to 0.000
0.000 to 1.000
0.00 to 3.00
0 to 120
7 to 10
5 to 40
0 to 1
1.0 to 3.0
1.0 to 5.0
1.0 to 10.0
0 to 2
0.0 to 5.0
DSABLE/ENABLE
DSABLE/ENABLE
RANGE
0 to 239
0 to 239
9600, 19200, 38400
RANGE
DSABLE/ENABLE
0 to 100
0 to 20
1 to 20
DSABLE/ENABLE
0 to 60
32 to 86
59 to 113
10 to 100
40 to 80
0 to 100
0 to 100
32 to 86
59 to 113
CL-11
UNITS
DEFAULT
0
0
°F
70.0
°F
45.0
3.0000
1.5000
degree
88.0
degree
27.0
degree
2.0
degree
109.0
°F
2.0
°F
1.5
°F
1.5
–0.010
0.010
2.00
sec
15
min
8
%
20
10
0
%
2.0
%
1.5
%
4.0
^F
1
^F
0.0
DSABLE
DSABLE
UNITS
DEFAULT
1
0
9600
UNITS
DEFAULT
DSABLE
%
100
^F
2
^F
5
min
DSABLE
30
°F
45
°F
95
%
100
%
60
%
80
%
45
°F
45
°F
95
VALUE
VALUE