Remote Terminal Access
C.4 Using the CRT-2 for Alter Status
C.4.1 Overview
This section shows how to Alter Status functions from a CRT-2.
NOTE: The panel must be in Local Terminal Mode (LocT) or Local Monitor Mode (LocM).
NOTE: See the NFS2-640 Programming Manual for instructions on enabling the CRT port.
Disable
Alarm/Pre-Alarm
Clear Verification
Clear History
Set Action/Alert
C.4.2 Accessing Alter Status Options
Access Alter Status function from the CRT-2 by following these steps.
1.
Turn on the CRT-2 connected to the control panel.
2.
Press the Alter Status function key. The control panel displays the Password screen.
Press <
ALTER STATUS
Enter Status CHange Password or Escape to Abort
3.
Enter the Status Change Password. The factory default Status Change Password is 11111.The
password does not display on the CRT-2. Five asterisks will appear in place of the password.
Press <1><1><1><1><1><
*****
The Alter Status Options menu appears.
1=Disable 2=Alarm/Prealarm 3=Clear Verification 4=Clear History 5=Alert/Action
From the Alter Status Options menu, you can select 1-5.
72
Function
Enable or disable detectors or modules.
Change the Alarm and Pre-Alarm levels of any addressable detector in the
system.
Clear the verification counter for all the addressable detectors in the system.
Clear the contents of the History buffer.
Set the Pre-Alarm for Alert or Action.
Table C.5 Alter Status Functions
>
>
ENTER
Using the CRT-2 for Alter Status
Lets you...
NFS2-640 Operations P/N 52743:L4 06/10/19