Read Status Operation
4.4 Viewing and Printing a Read Status
To view or print Read Status information follow the instructions below:
Option
Read Point
Print Points
Read History
Print History
Read Alarm History
Print Alarm History
NOTE: If attempting to read a point that is not installed, the control panel displays "Not Installed".
During all Read Status operations (except print operations) the control panel starts a 2-minute timer
each time you press a key. If the control panel does not detect a key press for 2 minutes, the control
panel exits Read Status and returns to the "System Normal" display.
In Read Status, you can also do the following:
Press the
Press the S
4.4.1 How to View Read Status of Devices, Zones, & System Settings
Overview
Read Point options 0, 2, and 4 in the Read Status Screen let you display and view information for
devices and zones programmed into the control panel, as well as view system and annunciator set-
tings. This section provides instructions and sample displays so you can view Read Status.
Topics covered in this section:
Intelligent Detectors
Control/relay and Monitor
modules
NAC
Software Zones (Z01-Z99)
Special Zones (F0-F9, FA- FC)
Releasing Zones (R0-R9)
System Functions
Annunciator Selections
42
Press
0 key,
key
ENTER
1 key,
key
ENTER
2 key,
key
ENTER
3 key,
key
ENTER
4 key,
key
ENTER
5 key,
key
ENTER
key to delete the previous entry.
ESC
R
key to abort Read Status.
YSTEM
ESET
To view Read Status for
Lets you
View information for a detector, module, NAC or zone
Print information for all installed points in the system
Display the total number of events in the History buffer and step
through each event in sequence
Print the contents of the History buffer (up to 800 events)
View a display of the number of alarms in the Alarm History buffer,
then scroll through each alarm event
Print the contents of the Alarm History buffer (up to 200 events)
Refer to
"How to View Read Status for a Detector" on page 43
"How to View Read Status for a Control/Relay or Monitor
Module" on page 44
"How to View Read Status for a NAC" on page 45
"How to View Read Status for a Software Zone (Z01-Z99)"
on page 46
"How to View Read Status for a Special Zone (F0-F9, FA-
FC)" on page 46
"How to View Read Status for a Releasing Zone (R0-R9)"
on page 47
"How to Read Status for System Functions" on page 47
"How to Read Status for Annunciator Selections" on
page 48
NFS2-640 Operations P/N 52743:L4 06/10/19