Use of the Controls
2.3.2 Signal Silence
Use the
SIGNAL SILENCE
connected to Notification Appliance Circuits. When pressed, the control panel does the following:
Turns off the panel sounder
Turns off all silenceable output circuits
Lights the
Sends a
terminals, and annunciators
Partial Signal Silence
When some active outputs are silenced and others remain constant, the
will flash.
NOTE: If Local Control is set to "0" (No Control) or "2" (Partial Control), the FACP will not
respond to
2.3.3 System Reset
Use the
SYSTEM RESET
lowing:
Clears ALL active inputs
Interrupts resettable power
Sends a "System Reset" message to the History buffer, and installed printers, CRT-2 terminals,
and FDU-80 annunciators
Decouples from Noti•Fire•Net, if connected, for 60 seconds to allow Cooperative Control By
Event (CCBE) to clear.
If any alarm or trouble exists after you press the
panel audio and visual indicators will reactivate.
NOTE: Trouble conditions will not clear and re-report upon reset.
NOTE: If Local Control is set to "0" (No Control), the FACP will not respond to
2.3.4 Drill
Use the
DRILL
To prevent accidental activation, you must press the
control panel does the following:
Turns on all silenceable NACs
Turns off the
Sends a Manual Evacuate message to the History buffer and installed printers, CRT-2
terminals, and FDU-80 annunciators
NOTE: If Local Control is set to "0" (No Control) or "2" (Partial Control), the FACP will not
respond to
14
key to silence the panel sounder and turn off all audio and visual devices
LED
SIGNALS SILENCED
message to the History buffer and installed printers, CRT-2
SIGNALS SILENCED
.
SIGNAL SILENCE
key to reset the control panel. When pressed, the control panel does the fol-
key to manually activate all silenceable outputs and Notification Appliance Circuits.
LED
SIGNALS SILENCED
.
DRILL
SIGNALS SILENCED
key, all NACs, control outputs, and
SYSTEM RESET
key for 2 seconds. When pressed, the
DRILL
NFS2-640 Operations P/N 52743:L4 06/10/19