Viewing and Printing a Read Status
How to Display the Total of Installed Devices
How to Display a Point or Zone for Read Status
To view a detector, press
To view a zone, press
To view a monitor or control/relay module, press
address,
To view a NAC, press
When you select a device or a zone, the control panel displays information for the device or zone,
but does not send this information to the serial ports or the History buffer.
How to View Read Status for a Detector
SLC number followed by three
digit address
next device
previous device
The display and descriptions of the fields are shown below:
Device status
Default CBE zone selection
Current alarm reading (percent)
Pre-Alarm sensitivity level
NFS2-640 Operations P/N 52743:L4 06/10/19
To view the total number of installed devices, enter the "Read Status" screen
by pressing the
will appear:
L 1 : 1 5 9 D e t s , 1 5 9 M o d s
P a n e l O u t p u t s : 6 4
S B L 1 : 0 0 0
From the "Read Status" screen, press 0, then press the
display the "Read Point Entry" screen as shown below:
Z O N E = Z , A A , E
M O D U L E = # , L M A A , E
DETECTOR
, zone number,
.
ENTER
OUTPUT
Type Code
N O R M A L S M O K E ( I O N )
E A S T E R N W I N G
Z 0 0 2
Alarm sensitivity level
Figure 4.1 Sample Detector Read Status Display
key, then 2, then A. A screen similar to the following
ENTER
L 2 : 0 5 5 D e t s , 0 4 7 M o d s
B e l l s : 0 4
S B L 2 : 0 0 0
D E T E C T O R = * , L D A A A , E
O U T P U T C K T = 8 , A A , E
, SLC number, detector SLC address,
.
ENTER
MODULE
, two-digit address, (for example 01 for B01, etc.),
From the "Read Status" screen, press 0, then press the
key. You can now view Read Status for a detector as follows:
press
, enter the SLC number followed by the three
DETECTOR
digit address, then press the
the status of detector 1D002: press
number (1), enter address 002, then press the
control panel now displays information about the detector, as
shown in Figure 4.1.
Label for the detector
I N T E N S I V E C A R E U N I T
0 0 1 % A 6 6 C V 0 0 1 D 0 0 2
Read Status Operation
ENTER
.
ENTER
, SLC number, module SLC
ENTER
key. For example, to read
ENTER
, enter the SLC
DETECTOR
key. The
ENTER
SLC Address (001-159)
D (detector)
SLC number (1 or 2)
Alarm Verification Time
(in seconds)
Alarm Verification selection:
V on; * off
Multidetector selection:
A, B, C, or * (not selected)
key to
.
ENTER
43