Water Flow Rate; Pre-Setting Of Valves; Balancing Strategy; Maintenance - Lindab Munio Installation Instructions Manual

Active chilled beam
Table of Contents

Advertisement

l ind ab | f o r a b et ter c lim at e
Installation instruction

6.4 Water flow rate

6.4.1 Pre-setting of valves

All the integrated control valves (plus feature) are delivered not set. The presetting has to be done on site.
For the presetting of valves, please see

6.4.2 Balancing strategy

Lindab recommends always balancing the water system to guarantee thermal comfort in all areas, to avoid noise
nuisance problems and to safe energy. A hydraulic balance is obvious to ensure that all the beams (panels or facade
units) in the system will always be supplied with their required (planned) water flow rates (calculated with
waterborne
calculator).
Lindab refers to the proportional method, where all beams (panels or facade units) are balanced to the same proportion
of the requested water flow rate.

7. Maintenance

The interval of cleaning depends on the indoor environment where the beam is placed. Under optimal conditions the
beams only need cleaning every 5 years.

Remove the outlet front grille (7.1).

Clean the top side of the battery and the mixing chamber with a vacuum cleaner.
Open the inlet face plate (7.2).
Clean the battery downside and the inlet faceplate inner part with a vacuum cleaner.
Only use lukewarm water and a mild detergent and a piece of wet cloth to clean the inlet face plate and the outlet
grille.
Open the inspection hatch behind the inlet faceplate (7.3).
Clean the air plenum and air connection with a vacuum cleaner.
7.1 Remove the outlet front grille

7.2 Open inlet faceplate

A
B
Opening outlet front grille and inlet faceplate.
34
LinFlow-A
(Angled) and
A
!
Warning: Sharp edges
Lindab reserves the right to make changes without prior notice
LinFlow-S
(Straight) water valves documentation.
B
Vacuum cleaner
2024-01-05
Munio
LindQST\
Dust-cleaner