Table 5-2 Ground cable specifications
Cross-Sectional Area S (mm
AC Power Cable Conductor
16 < S ≤ 35
35 < S
The values in this table are valid only if the PE cable and AC power cable use
the same conductor material. If this is not so, the cross-sectional area of the PE
cable conductor is to be determined in a manner which produces a conductance
equivalent to that which results from the application of this table.
Installing the PE Cable
Step 1 Crimp an OT terminal.
Step 2 Secure the PE cable using the ground screw.
Figure 5-7 Connecting a PE cable
Step 3 (Optional) To enhance the corrosion resistance of a ground terminal, apply silica
gel or paint around the terminal.
----End
Installing the AC Output Power Cable
Step 1 Remove the locking cap from the AC OUTPUT cable gland and then remove the
plug.
Step 2 Route the cable through the cable gland.
Issue 08 (2024-02-02)
2
) of the
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Cross-Sectional Area S
the PE Cable Conductor
S
≥ 16
P
S
≥ S/2
P
2
(mm
) of
P
48