Huawei SUN2000-50KTL-M0 User Manual page 108

Hide thumbs Also See for SUN2000-50KTL-M0:
Table of Contents

Advertisement

SUN2000-(50KTL-M0, 70KTL-INM0)
User Manual (India Edition)
Parameter
Shutdown at 0%
power limit
Plant active power
gradient (min/100%)
Average active power
filtering time (ms)
Active power change
gradient (%/s)
Fixed active power
derated (kW)
Active power
percentage derating
(%)
Reactive power
change gradient
(%/s)
Power factor
Reactive power
compensation (Q/S)
Night-time reactive
power output
Enable reactive
power parameters at
night
Issue 08 (2024-02-02)
Description
If this parameter is set to Enable, the
SUN2000 shuts down after receiving
the 0% power limit command. If this
parameter is set to Disable, the
SUN2000 does not shut down after
receiving the 0% power limit
command.
Specifies the rate of active power rise
due to sunlight changes.
Specifies the period of active power
rise due to sunlight changes. This
parameter is used with Plant active
power gradient.
Adjusts the change speed of the
SUN2000 active power.
Adjusts the active power output of the
SUN2000 to a fixed value.
Adjusts the active power output of the
SUN2000 to a percentage.
Specifies the change speed of the
inverter reactive power.
Adjusts the SUN2000 power factor.
Adjusts the SUN2000 output reactive
power.
In some specific application scenarios,
a power grid company requires that
the inverter can perform reactive
power compensation at night to
ensure that the power factor of the
local power grid meets requirements.
When this parameter is set to Enable,
the inverter outputs reactive power
based on the setting of Reactive
power compensation at night.
Otherwise, the inverter executes the
remote scheduling command.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Remarks
N/A
N/A
N/A
Adjust the active power based
on the percentage of the rated
apparent power.
This parameter is displayed if
Remote power schedule is set
to Enable.
If this parameter is set to 100,
the SUN2000 delivers power
output based on the maximum
output power.
N/A
N/A
N/A
This parameter is displayed
when Isolation settings is set to
Input ungrounded, with TF.
This parameter is displayed
when Night-time reactive
power output is set to Enable.
100