For the SUN2000 that supports built-in PID repair, when Built-in PID running
mode is set to Repair, there is repair voltage between PV modules and the ground
at night. If you need to maintain PV modules at night, power off the SUN2000 to
avoid electric shocks.
Protection
Item
Input DC switch
Anti-islanding protection
Output overcurrent
protection
Input reverse polarity
protection
PV string fault detection
DC surge protection
AC surge protection
Insulation resistance
detection
Residual current
monitoring unit (RCMU)
Overvoltage category
Built-in PID repair
Note c: When the SUN2000 is disconnected from the grid and stops working,
the built-in PID can achieve the PV– positive offset of the PV module. (PV–
positive offset refers to raising the voltage between PV– and the ground to
above 0 V through voltage compensation.) When designing a power plant,
confirm with the PV module manufacturer that the anti-PID voltage
compensation direction of the PV module is the same as the direction of the
PV– positive offset. Otherwise, PV modules may be damaged.
For the SUN2000 that supports built-in PID repair, when Built-in PID running
mode is set to Repair, there is repair voltage between PV modules and the ground
at night. If you need to maintain PV modules at night, power off the SUN2000 to
avoid electric shocks.
Issue 08 (2024-02-02)
CA UTION
c
CA UTION
Copyright © Huawei Technologies Co., Ltd.
SUN2000-70KTL-INM0
Not supported
10 Technical Specifications
SUN2000-50KTL-M0
Supported
Supported
Supported
Supported
Supported
Type II
Type II
Supported
Supported
PV II/AC III
Optional