Drain Hose Installation

The diameter of the drain hose should be equal to or bigger than the connection pipe's.
(The diameter of polythene pipe: Outer diameter 25mm wall thickness 1.5mm)
Drain hose should be short and drooping gradient should be at less 1/100 to prevent the formation
of air bubble.
If drain hose cannot hasn't enough deooping gradient. drain raising pipe should be added.
To prevent bending of the drain hose, the distance between hoisting stands should be 1 to 1.5m.
Use the drain hose and clamp attached. Insert the drain hose to the drain cent, and then tighten the clamp.
Entwine the big sponge on the clamp of drain hose to insulate heat. (Figure 7.1)
Heat insulation should be done to indoor drain hose.
Sponge (gray)
The installation height of the drain raising pipe should be less than 280mm.
The drain raising pipe should form a upright angle with the unit, and distance to unit should notbeyond
300mm.
Within 300mm
Ceiling
8
1-1.5 m
O (Correct) 1/100 or more gradient
Clamp
Drain hose
Drain hose
(Accessory)
www.ttair.co.th | Tel : 02-385-0728 | E-mail : sales@ttair.co.th | LINE ID : @ttair
Figure 7
Sponge (Attachment)
Clamp (Attachment)
Figure 7.1
Roof
1-1.5
Drain raising hose
220 mm
Clamp (Accessory)
Figure 8
X (Wrong)
Below 4mm.
Hoisting stand
Below 280mm
Below 500mm
MCC-SVN01A