Error Codes When Performing A Test Run; Disposal - Daikin Sky Air Active Series Installation Manual

Hide thumbs Also See for Sky Air Active Series:
Table of Contents

Advertisement

10 Disposal

#
Action
3
Change the position.
4
Press.
5 Stop the test run.
#
Action
1
Press at least 4 seconds.
2
Select Test Operation.
3
Press.
9.3
Error codes when performing a
test run
If the installation of the outdoor unit has NOT been done correctly,
the following error codes may be displayed on the user interface:
Error code
Nothing displayed
▪ The wiring is disconnected or there is a
wiring error (between power supply and
(the currently set
outdoor unit, between outdoor unit and
temperature is not
indoor units, between indoor unit and
displayed)
user interface).
▪ The fuse on the outdoor unit PCB has
blown out.
E3, E4 or L8
▪ The stop valves are closed.
▪ The air inlet or air outlet is blocked.
E7
There is a missing phase in case of three-
phase power supply units.
Note: Operation will be impossible. Turn
OFF the power, recheck the wiring, and
switch two of the three electrical wires.
L4
The air inlet or air outlet is blocked.
U0
The stop valves are closed.
U2
▪ There is a voltage imbalance.
▪ There is a missing phase in case of
three-phase power supply units. Note:
Operation will be impossible. Turn OFF
the power, recheck the wiring, and switch
two of the three electrical wires.
U4 or UF
The inter-unit branch wiring is not correct.
UA
The outdoor and indoor unit are
incompatible.
Installation manual
16
Result
If the airflow flap of the
indoor unit moves,
operation is OK.
If not, operation is not OK.
The home menu is
displayed.
Result
The Service Settings menu
is displayed.
Service Settings
1/3
Test Operation
Maintenance Contact
Field Settings
Demand
Min Setpoints Differential
Group Address
Return
Setting
The unit returns to normal
operation, and the home
menu is displayed.
Possible cause
NOTICE
▪ The reversed phase protection detector of this product
only
functions
when
Consequently
reversed
performed during normal operation of the product.
▪ The reversed phase protection detector is designed to
stop the product in the event of an abnormality when
the product is started up.
▪ Replace 2 of the 3 phases (L1, L2, and L3) during
reverse-phase protection abnormality.
10
Disposal
This unit uses hydrofluorocarbon. Contact your dealer when
discarding this unit. It is required by law to collect, transport and
discard the refrigerant in accordance with the "hydrofluorocarbon
collection and destruction" regulations.
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
the
product
starts
up.
phase
detection
is
not
AZAS100~140MUV/Y
Sky Air Active-series