Electrical Connection
4.3

Battery Connection

ESS inverter now only supports the lithium/lead-acid battery. The recommended lithium battery
brands are as follows: PYLON LPF, Aoboet LPF, Dyness LPF, UZENERGY L051100-A.
This part in this manual only describe the battery connection on inverter side. If you need more detailed
connection information about the battery side, please refer to the manual of the battery you used.
Before connecting to battery, please install a separate DC breaker (150A; not equipped) between
inverter and battery. This ensures the inverter can be securely disconnected during maintenance.
A
A. Diameter
B. Cross Section
C. Strip Length
a
Hydraulic Pressure
Crimper
d
WARNING
Battery Communication Connection
If the battery type is lithium battery which need communication between the inverter and
battery management system (BMS), the connection must be installed. Please refer to
section 4.6.1 for details.
B
C
10 ~ 12mm
25mm²
~10mm
b
DC Breaker 150A
It is recommended that the
battery cable be less than or
equal to 3 m.
This product is not equipped
e
with DC breakers.
Reverse polarity will damage the inverter!
Be careful of electric shock and chemical hazards!
To reduce risk of injury, please use the suitable recommended
cable size.
Single-phase ESS Inverter User Manual
c
Click
f
+ Red Cable
- Black Cable
19