4.3

Battery Connection

ESS inverter now only supports the lithium/lead-acid battery. The recommended lithium battery brands are
as follows: PYLON LPF, Aoboet LPF, Dyness LPF, UZENERGY L051100-A.
This part only describes the battery connection on inverter side. If you need more detailed connection
information about the battery side, please refer to the manual of the battery you used.
Before connecting to battery, please install a separate DC breaker (150A; not equipped) between inverter
and battery. This ensure the inverter can be security disconnected during maintenance.
A
A. Diameter
B. Cross Section
C. Strip Length
a
Hydraulic Pressure
Crimper
d
WARNING
Battery Communication Connection
If the battery type is lithium battery which need communication between the inverter and battery
management system (BMS), the connection cable must be installed. Please refer to section 4.6.1 for details.
B
C
10 ~ 12mm
25mm²
~10mm
b
DC Breaker 150A
OFF
It is recommended that the
battery cable be less than or
equal to 3m.
e
Polarity reverse will damage the inverter!
Be careful of electric shock and chemical hazards!
To reduce risk of injury, please use the suitable recommended cable size.
Click
f
18
4 Electrical Connections
4 Electrical Connections
c
Red Cable
Black Cable