Service/Configuration Menu - Viessmann VITOCAL 100-AW Installation, Service And Operating Instruction

Table of Contents

Advertisement

Vitocal 100-AW AM2V Installation, Service and Operating

Service/Configuration Menu

9:37 Thu 22.04.2021
Service
Control Strat.
Room Temp. Offset
Air Vent Mode
Measuring Unit
Changes in the configuration menu are possible
after entering an access code. When prompted
for an access code, turn the navigation dial to the
required code and confirm the code by pressing
the dial. If you want to exit from the code request
screen, hold the navigation dial or wait until
automatic return to main function screen.
Code: 987
Scroll through the menu with the navigation dial
and press the navigation dial to select. When
complete select 'End' to return to the Service
menu.
Heating:
Control Strat.:
H Heating Curve Operation - Temperature in is
calculated on the basis of outside temperature
and room temperature based on schedule.
H Constant Temperature - Supply temperature
MAN, set individual for Circuit 1 and Circuit 2.
Glycol Loop Heat Exchanger:
H Yes - there is an additional heat exchanger in the
system
H No - there is no additional heat exchanger in the
system.
Frost protection:
H Yes - if the temperature in the building drops
below 45LF (7LC) in the stand-by mode and the
outside temperature is lower than 36LF (2LC),
heating will be turned on ,
H No - protection is disabled.
Electric Heater Delay:
Operating
53