Safety Valve - Viessmann VITOCAL 100-AW Installation, Service And Operating Instruction

Table of Contents

Advertisement

Vitocal 100-AW AM2V Installation, Service and Operating

Safety Valve

A
E
F
G
Legend
A Supply from Outdoor Unit
B 1 Inch Brass 90 Degree Elbow
C 1 X 8 Inch Long Brass Nipple
D Microbubble Air Separator
E 1 X 1 X c Inch Brass Reducing Tee
F c Inch Brass 90 Degree Street Elbow
G c Inch Brass Close Nipple
H 30 PSI Pressure Relief Valve
I Return to Outdoor Unit
1
WARNING
Do not install an isolation valve between heat
pump and pressure relief valve. The discharge pipe
for the pressure relief valve must be oriented to
prevent scalding of attendants. Pipe pressure relief
valve discharge pipe close to floor drain. Never
pipe discharge pipe to the outdoors.
1
IMPORTANT
Install the (approved) factory supplied pressure
relief valve. Removal of air from the system must
occur via use of air vent(s) in the system supply.
To ensure the heat pump can be purged of all air,
ensure supply/return water lines do not contain
restrictive piping where air could be trapped.
C
B
D
I
H
A
Installing the pressure relief valve:
1. Use the supplied fittings to install the pressure
relief valve on the Supply from Outdoor Unit.
Minimum connection diameters:
Pressure relief valve ..................................... c in.
Discharge pipe ............................................ c in.
Maximum operating pressure: 30 PSI (2 bar)
Minimum operating pressure: 8 PSI (0.5 bar)
Installing the discharge pipe:
1. Install discharge pipe on pressure relief valve in
such a way that...
- the end of the pipe is not threaded.
- the pressure relief discharge pipe
approximately 6 in. (150 mm) above the ground.
Ensure that...
- there is no shutoff valve installed in the
discharge pipe.
- discharge pipe diameter is not reduced.
Connections
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

0200280340043051078

Table of Contents