4 Mounting and Installation

As the room sensor is generally mounted onto a conduit box, for accurate measurement results it is important
to tighten the conduit box for avoiding false air ingress (along the electrical tubes inside the wall) into the room
sensor enclosure.
PLEASE NOTE
In order to protect the front cover and the electronics from typical construction site pollution (such as painting
of the walls) the front cover should be snapped on only after the construction works are completed.
Please mind the following rules of thumb for sensor positioning:
Mount the Sensor 2 m (6.6 ft) away from outlets and intakes
Mount the Sensor at a height of 1.5 m (5 ft) (half of room height)
Avoid direct sunlight from window
Avoid restricted airflow
Avoid close proximity to heat sources
Avoid heat accumulation
Avoid draught
The electronics is located in the front cover, which can be easily snapped on/off once the back cover is fixed onto
the wall and wired.
C
Opening the enclosure
B
Press to release the latch A till the enclosure can be
opened.
Closing the enclosure
Set the front cover into flutes B, rotate it like C and press it
onto the back cover till the latch A snaps in.