Connecting the Power Wiring / Communications Cable
Best practice dictates using ring or spade terminals to terminate power wiring at the power terminal block. if ring terminals or spade clips are
not available, then:
• Do not terminate different gauge wires to the power terminal block. (slack in the wiring may generate heat.)
• When terminating wires of the same thickness, follow the instructions demonstrated in the figures below.
• Firmly attach the wire; secure in a way to prevent external forces from being imparted on
the terminal block.
• Use an appropriately sized screwdriver for tightening the terminals.
• Do not overtighten the connections; overtightening may damage the terminals.
Figure 95: Proper and improper Power Wiring Connections.
Terminate multiple power wires of
the same gauge to both sides.
If power wires are not properly terminated and firmly attached, there is risk of fire, electric shock, and physical injury or death.
• Never apply line voltage power to the communications cable terminal block. If contact is made, the PCBs may be damaged.
• Always include some allowance in the wiring length when terminating. Provide some slack to facilitate removing the electrical panels
while servicing.
Do not terminate two wires on
one side.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
WIrInG ConneCtIons
General Information
Figure 93: Close up of a typical ring terminal.
Ring Terminal
Figure 94: Close up of the indoor Unit terminal
Block.
:Copper Wire
Do not terminate different gauge
wires to a terminal block.
Power Wiring
WIRING CONNECTIONS | 221