Page 1
ADL3000-E-A Installation and operation instruction V1.1 ACREL Co,.Ltd...
Page 2
Declare The copyright is the property of Acrel. Any information in any paragraph or section cannot be extracted, copied or otherwise reproduced or propagated. Otherwise offenders shall take all consequences. All rights are reserved. Acrel reserves the right to modify the product specifications herein without notification.
Page 3
Time Revision Journal Remarks 2023.03.14 V1.0 the first edition. 2023.03.30 V1.1 Harmonic measurement and communication changed to standard configuration...
. It is fitted with RS485 communication port and adapted to MODBUS-RTU. ADL3000-E-A can be used in all kinds of control systems, SCADA systems and energy management systems. All meters meet the related technical requirements of electricity power meter in the IEC62052-11、IEC62053-22 standards...
Accuracy class Error±0.2% 3~10(80)A Input current Min:0.1A,Standard:10A,Max:80A Current Consumption <1VA(Single phase rated current) Accuracy class Error±0.2% Power Active, reactive, apparent power, error±0.5℅ Frequency 45~65Hz, Error±0.2% Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy Energy class 2) 1 active optocoupler output, Resistive load(Voltage is not more Energy pulse output than 24V, current is not more than 5mA)...
Suivez tous les conseils de sécurité derrière ce signe pour éviter d’éventuelles blessures ou décès. 6.2 Wiring sample of voltage and current Fig2 Three phase four lines direct connect Note : ADL3000-E-A can adopt o access methods: three-phase four wire(Fig2) .
Page 8
product drawing Port Description Remark UA Volatge Input /IA Currten Input L1’ IA Currten Output UB Volatge Input /IB Currten Input L2’ IB Currten Output UC Volatge Input /IC Currten Input L3’ IC Currten Output Neutral Line Recommended cross section:1...25 mm2 (17...3 AWG) ...
Page 9
WARNING Use copper wire rated for 500V. Minimum temperature rating of the cable to be connected to the field wiring terminals, 80 °C. Failure to follow these instructions can result in death, serious injury, or equipment damage. AVERTISSEMENT Utilisez un fil de cuivre évalué...
The switch input adapts the method of on-off signal input and powered by outer power supply. It can be gotten by meter when there is a change of on or off via a switching input module. The parameter of switching input can not only get and show the state of local switching information but also achieve the communication via RS485, which called “remote information”...
Page 11
A, B, C phase. Note: 1 All the display menus above are in the model of ADL3000-E-A three phases four lines with multi-tariff rate function and can be changed by the keys. 2 There will not be power or power factor on each phase and will only show total power and power factor (Active, reactive, apparent) under the three phase three lines.
Voltage on A phase is 123.4V Current on A phase is 12.34A Note: There are parts of the display function, and other menus are familiar with the example above. The customers can understand the meaning refer to the above examples. 9.3 Key Menu Press at any main menu and get in “PASS”...
Page 13
bps、9600bps and 19200 bps. The parity is None. The meter needs shielded twisted pair conductors to connect. Customers should consider the whole network’s parameters such like communication wire’s length, the direction, communication transformer and network cover range, etc. Note: Wiring should follow the wiring requirements; Connect all the meter in the RS485 net work even some do not need to communication, which is benefit for error checking and testing;...
Page 14
017FH Total power factor 10.2 Sub harmonic data ADL3000-E-A has function of harmonic. The function include 31 harmonic statistics of voltage and current, harmonic voltage and current of each phase apparently, harmonic active/reactive power of each phase apparently, fundamental voltage and current of each phase apparently and fundamental active/reactive power of each phase apparently.
Page 15
each phase 05DFH THDUc 05E0H THDIa Keep 3 decimal places 05E1H THDIb 05E2H THDIc Harmonic voltage on 05E3H THUa × 0601H THUb × × 061FH THUc Keep 3 decimal places Harmonic current on 063DH THIa × 065BH THIb × 0679H THIc ×...