Acrel ADL3000-E-A Installation And Operation Instruction Manual

Advertisement

Quick Links

495
ADL3000-E-A
Installation and operation instruction V1.1
ACREL Co,.Ltd

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADL3000-E-A and is the answer not in the manual?

Questions and answers

Summary of Contents for Acrel ADL3000-E-A

  • Page 1 ADL3000-E-A Installation and operation instruction V1.1 ACREL Co,.Ltd...
  • Page 2 Declare The copyright is the property of Acrel. Any information in any paragraph or section cannot be extracted, copied or otherwise reproduced or propagated. Otherwise offenders shall take all consequences. All rights are reserved. Acrel reserves the right to modify the product specifications herein without notification.
  • Page 3 Time Revision Journal Remarks 2023.03.14 V1.0 the first edition. 2023.03.30 V1.1 Harmonic measurement and communication changed to standard configuration...
  • Page 4: Table Of Contents

    Content 1 General..............................1 2 Type description............................ 1 3 Function description..........................1 4 Technical parameter..........................1 5 Dimension drawings..........................2 6 Wiring and installation.......................... 3 7 Maintenance............................6 8 Function description..........................6 9 Operation and display..........................6 10 Communication description........................ 8...
  • Page 5 . It is fitted with RS485 communication port and adapted to MODBUS-RTU. ADL3000-E-A can be used in all kinds of control systems, SCADA systems and energy management systems. All meters meet the related technical requirements of electricity power meter in the IEC62052-11、IEC62053-22 standards...
  • Page 6 Accuracy class Error±0.2% 3~10(80)A Input current Min:0.1A,Standard:10A,Max:80A Current Consumption <1VA(Single phase rated current) Accuracy class Error±0.2% Power Active, reactive, apparent power, error±0.5℅ Frequency 45~65Hz, Error±0.2% Active energy(Accuracy class:0.5, 1), reactive energy(Accuracy Energy class 2) 1 active optocoupler output, Resistive load(Voltage is not more Energy pulse output than 24V, current is not more than 5mA)...
  • Page 7 Suivez tous les conseils de sécurité derrière ce signe pour éviter d’éventuelles blessures ou décès. 6.2 Wiring sample of voltage and current Fig2 Three phase four lines direct connect Note : ADL3000-E-A can adopt o access methods: three-phase four wire(Fig2) .
  • Page 8 product drawing Port Description Remark UA Volatge Input /IA Currten Input L1’ IA Currten Output UB Volatge Input /IB Currten Input L2’ IB Currten Output UC Volatge Input /IC Currten Input L3’ IC Currten Output Neutral Line Recommended cross section:1...25 mm2 (17...3 AWG) ...
  • Page 9 WARNING Use copper wire rated for 500V.  Minimum temperature rating of the cable to be connected to the field wiring terminals, 80 °C.  Failure to follow these instructions can result in death, serious injury, or equipment damage. AVERTISSEMENT Utilisez un fil de cuivre évalué...
  • Page 10 The switch input adapts the method of on-off signal input and powered by outer power supply. It can be gotten by meter when there is a change of on or off via a switching input module. The parameter of switching input can not only get and show the state of local switching information but also achieve the communication via RS485, which called “remote information”...
  • Page 11 A, B, C phase. Note: 1 All the display menus above are in the model of ADL3000-E-A three phases four lines with multi-tariff rate function and can be changed by the keys. 2 There will not be power or power factor on each phase and will only show total power and power factor (Active, reactive, apparent) under the three phase three lines.
  • Page 12 Voltage on A phase is 123.4V Current on A phase is 12.34A Note: There are parts of the display function, and other menus are familiar with the example above. The customers can understand the meaning refer to the above examples. 9.3 Key Menu Press at any main menu and get in “PASS”...
  • Page 13 bps、9600bps and 19200 bps. The parity is None. The meter needs shielded twisted pair conductors to connect. Customers should consider the whole network’s parameters such like communication wire’s length, the direction, communication transformer and network cover range, etc. Note: Wiring should follow the wiring requirements; Connect all the meter in the RS485 net work even some do not need to communication, which is benefit for error checking and testing;...
  • Page 14 017FH Total power factor 10.2 Sub harmonic data ADL3000-E-A has function of harmonic. The function include 31 harmonic statistics of voltage and current, harmonic voltage and current of each phase apparently, harmonic active/reactive power of each phase apparently, fundamental voltage and current of each phase apparently and fundamental active/reactive power of each phase apparently.
  • Page 15 each phase 05DFH THDUc 05E0H THDIa Keep 3 decimal places 05E1H THDIb 05E2H THDIc Harmonic voltage on 05E3H THUa × 0601H THUb × × 061FH THUc Keep 3 decimal places Harmonic current on 063DH THIa × 065BH THIb × 0679H THIc ×...
  • Page 16 ADL3000-E-B Installation and operation instruction V1.0 ACREL Co,.Ltd...
  • Page 17 Declare The copyright is the property of Acrel. Any information in any paragraph or section cannot be extracted, copied or otherwise reproduced or propagated. Otherwise offenders shall take all consequences. All rights are reserved. Acrel reserves the right to modify the product specifications herein without notification.
  • Page 18 Content 1 General ............................1 2 Type description ..........................1 3 Function description ........................1 4 Technical parameter ........................2 5 Outline ............................2 6 Wiring and installing ........................3 7 Function description ........................8 8 Operation and display ........................ 8 9 Communication description ....................10...
  • Page 19: General

    . It is fitted with RS485 communication port and adapted to MODBUS-RTU. ADL3000-E-A can be used in all kinds of control systems, SCADA systems and energy management systems. All meters meet the related technical requirements of electricity power meter in the IEC62052-11、...
  • Page 20: Technical Parameter

    “■” means standard, “□” means optional. Note: Harmonic is a standard while choosing outlay transformer, optional for another situation. 4 Technical parameter Specification 3 phase 4 wires, Earthed Reference voltage 3~66/115V、3~220/380V(Two sizes) Input voltage ±30% torlanc Voltag <10VA (Single phase) Consumption (Rate current or power for power input <10VA(Single phase)) Impedance...
  • Page 21: Wiring And Installation

    Fig 1 connect via CT Note : Labels can only be wiped with dry cloth. 6 Wiring and installation 6.1 Safety instruction Information for your own safety This manual does not contain all of the safety measures for operation of the equipment (module, device), because special operating conditions, and local code requirements or regulations may necessitate further measures.
  • Page 22 Obey all safety messages that follow this symbol to avoid possible injury or death. C ’ est un signe d ’ avertissement de sécurité. Utilisé pour vous alerter sur les risques potentiels de blessures corporelles. Suivez tous les conseils de sécurité derrière ce signe pour éviter d’éventuelles blessures ou décès.
  • Page 23 Ib Currten Input Ib Currten Output Ic Currten Input Ic Currten Output Recommended cross section:1...16 mm2 (17...5 AWG)  The necessary torque is 2 N•m (18 lb-in) .  WARNING  Use copper wire rated for 500V. Minimum temperature rating of the cable to be connected to the field wiring terminals, 80 °C. ...
  • Page 24 or equipment damage. AVERTISSEMENT Utilisez un fil de cuivre évalué pour 500V.  Température nominale minimale du câble à connecter aux bornes de câblage sur le terrain,  80 °C. Le non-respect de ces instructions peut entraîner la mort, des blessures graves ou des dommages à...
  • Page 25: Maintenance

    Fig 4 Communication, Swtich input The switch input adapts the method of on-off signal input and powered by outer power supply. It can be gotten by meter when there is a change of on or off via a switching input module. The parameter of switching input can not only get and show the state of local switching information but also achieve the communication via RS485, which called “remote information”...
  • Page 26: Function Description

    8 Function description 8.1 Measurement The meter can measure all electrical parameters such as voltage, current, active power, reactive power, apparent power, power factor, frequency, 31 harmonic and total harmonic. The value format of voltage, current, frequency and power are listed as below. Example: U = 220.1V,f = 49.98Hz, I = 1.99A,P = 0.439kW 8.2 Calculating The meter can calculate the current active energy, forward active energy, reversing active...
  • Page 27 energy, forward active energy on A, B, C phase. Note: 1 All the display menus above are in the model of ADL3000-E-B three phases four lines with multi-tariff rate function and can be changed by the keys. 2 There will not be power or power factor on each phase and will only show total power and power factor (Active, reactive, apparent) under the three phase three lines.
  • Page 28: Communication Description

    “0000”, and enter the code. If you enter a wrong code, it will show “fail” and back to main menu; and if you enter a right code, you can set the parameter. After setting the parameter and press , it will show “save” and save the change by pressing in “yes”...
  • Page 29 10.1 ADDR list MODBUS-RTU protocol has 03H and 10H command to read and write registers respectively. The following chart is registers’ address list: Address Variable Length Notes E=data*PT*CT*0.0 0000H Current total active energy Data:data read in 000AH Current forward active total energy the communication, Pt:voltage ratio 0014H...
  • Page 30 0078H Voltage between A-B U=data*PT*0.1 0079H Voltage between C-B Unit:V 007AH Voltage between A-C 0087H Forward active energy of A phase 0089H Forward active energy of B phase 008BH Forward active energy of C phase 008DH Voltage transfer(PT) 008EH Current transfer(CT) State of DIDO, over-voltage, loss- 008FH voltage...
  • Page 31 PQS=data*PT*CT* 0168H Active power of C phase 0.001 Unit:KW(active) 016AH Total active power kVar(reactive) kVA(apparent) 016CH Reactive power of A phase Active power and reactive power are 016EH Reactive power of B phase signed data, please set them as signed 0170H Reactive power of C phase variables.
  • Page 32 0601H THUb × × 061FH THUc Keep 3 decimal places 063DH THIa Harmonic current on × 065BH THIb × × 0679H THIc Keep 2 decimal places 0697H Fundamental voltage on A phase 0698H Fundamental voltage on B phase 0699H Fundamental voltage on C phase 069AH Harmonic voltage on A phase Keep 1 decimal places...
  • Page 33 06B2H Total harmonic reactive power...